HLP-C100 Series
HLP-C100 Series Operating Manual
-
27
-
Item
Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
C04.61
Bypass Speed
From [Hz]
0.0~400.0
Hz
0.0
C04.63
Bypass Speed
To [HZ]
0.0~400.0
Hz
0.0
Pa
ra
m
ete
r G
ro
up
0
5: D
ig
ita
l I
n/O
ut
C05.10
Terminal FOR
Digital Input
0: No operation;
1: Reset; 2: Coast
inverse; 5: DC-brake
inverse; 6: Stop
inverse; 8: Start;
10: Reversing; 11: Start
reversing; 14: Jog;
15: Preset ref bit0;
16: Preset ref bit1;
17: Preset ref bit2;
28: Catch up; 29: Slow
down; 34: Ramp
bit0; 35: Ramp bit1;
36:Ramp bit2;
8
C05.11
Terminal REV
Digital Input
10
C05.12
Terminal DI1
Dgital Input
15
C05.13
Terminal DI2
Digital Input
16
C05.14
Terminal DI3
Digital Input
17
C05.40
Relay
Function(FA-
FB
、
FB-FC)
0: No operation;
5: Drive running;
9: Alarm; 10: Alarm
or Warning; 15: Out
of f requency rang;
16: Below f requency,
low; 17: Above
f requency, high;
21: Thermal warning;
24: Ready, voltage
ok; 25: Reverse;
26: Bus ok; 28: Brake,
no brake warning;
53: No alarm;
55: Running reverse;
0
C06.10
Terminal VI
Low Voltage
0.00~9.99
V
0.07
C06.11
Terminal VI
High Voltage
0.10~10.00
V
10.00
C06.12
Terminal VI
Low Current
0.00~19.99
mA
0.14