HLP-C100 Series Operating Manual
HLP-C100 Series
-
62
-
Option: [0] Off, Disable the overmodulation f unction to avoid torque ripple on
the motor shaf t;
[1] On, Connects the overmodulation f unction to obtain an output
voltage up to 15% greater than mains voltage;
Function: This feature allows more accurate speed control near and over
*C14.03 Function Description
Range
Unit
Default Setting
Over modulation
0~1
1
Function: Specif y maximum permissible delay time between transmitting a
request and receiving a respond. Exceeding this time delay will cause
word timeout.
C08.36 Function Description
Range
Unit Default Setting
Max. Response Delay 0.010~10.000
s
5.000
Function: Enter the value to be used as bus-feedback. Hex-value 4000H
corresponds to 100% feedback/range is +/-200%.
C08.94 Function Description
Range
Unit
Default Setting
Bus Feedback 1
-32768~32767
0
C08.9* Bus Jog/Feedback
7.10 Parameter Group 14: Special Functions
Option: [2] - [6] 2-6kHz;
[7] 8kHz;
[8] 10kHz;
[9] 12kHz;
[10] 16kHz;
Description of choice: Switching f requency of the f requency converter has a
signi
fi
cant in
fl
uence to the inverter and the motor. Select appropriate
switch f requency can help to adjust acoustic noise f rom the motor
、
power consumption and the inverter ef f iciency. When switching
f requency increases, the consumption and the noise of the motor are
reduced, but the drive’s temperature will increase, and motor leakage
and the interference to the external device will increase; the contrary
the opposite.
C14.01
Function Description
Range
Unit
Default Setting
Switching Frequency
0~10
5