HLP-C100 Series Operating Manual
HLP-C100 Series
-
64
-
Function: Enter time interval f rom trip to start of automatic reset f unction
af ter a warning/alarm.
Description of Choice: This parameter is active when C14.20, Auto Reset, is set
to Automatic reset [1]-[13].
C14.21
Function Description
Range
Unit
Default Setting
Automatic Restart Time
0~600
s
10
Option: [0] Normal operation;
[2] Initialization, initialise all the parameters except information about
the inverter itself and the recorded parameters.
[3] Backup user settings;
[4] Recover user settings;
Function: Af ter modif ying the inverter parameters based on the f unctional
requirements, OEM manufacturers can set C14.22 = 3 to backup
settings. If the end user modif y parameters and can not be self-
recovery, it can be recovered by setting C14.22 = 4 or pressing "OFF"
key on LCP 5 seconds.
C14.22
Function Description
Range
Unit
Default Setting
Operation Mode
0~4
0
Option: [0] Disable, Trip lock fault reset do not need power off
[1] Enable, Trip lock fault reset need power off
C14.23
Function Description
Range
Unit
Default Setting
Trip lock
0~1
0
Option: [0] Disable;
[1] Enable;
Function: This f unction ensures the output voltage is independent of any
voltage
fl
uctuations in the DC link . Low torque ripple. In some cases,
this dynamic compensation may cause resonance problems in DC link
circuit and then this f unction should be disabled.
*C14.51 Function Description
Range
Unit
Default Setting
DC-LinkVoltage
Compensation
0~1
0
C14.5* DC Voltage Compensation