GigaVUE-HC3 equipment or subassembly are suitable for connection to intrabuilding
or unexposed wiring or cabling only. The intra-building port(s) of the equipment or
subassembly MUST NOT be metallically connected to interfaces that connect to the
OSP or its wiring. These interfaces are designed for use as intra-building interfaces
only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 6) and require
isolation from the exposed OSP cabling. The addition of Primary Protectors is not
sufficient protection in order to connect these interfaces metallically to OSP wiring.
Intrabuilding Ports (RJ45)
WARNING
: The intrabuilding ports (RJ45) shall be connected to shielded and
grounded cables at both ends.
Class A2 Voltage Accessibility
The GigaVUE-HC3 shall be located in a restricted access location where only crafts
personnel are allowed access.
Class B Voltage Accessibility
The GigaVUE-HC3 shall be located in a restricted access location where only crafts
personnel are allowed access.
Equipment Grounding Systems
The GigaVUE-HC3 shall be installed and connected to the (CBN).
Communication Equipment Grounding
The GigaVUE-HC3 is suitable for connection to the (Central Office and CPE).
Bonding of Battery Return (BR) Input Terminals
The battery returns of the GigaVUE-HC3 shall be connected as (DC-I).
Connections
a.
The GigaVUE-HC3 shall be grounded via a copper ground conductor #6 AWG
for CPE installation.
Summary of Contents for GigaVUE-HC3
Page 1: ...GigaVUE HC3 Hardware Installation Guide GigaVUE OS 5 7 00...
Page 46: ...46 GigaVUE HC3 Hardware Installation Guide...
Page 70: ...70 GigaVUE HC3 Hardware Installation Guide...
Page 112: ...112 GigaVUE HC3 Hardware Installation Guide...
Page 126: ...126 GigaVUE HC3 Hardware Installation Guide...
Page 132: ...132 GigaVUE HC3 Hardware Installation Guide...