XT120C – XT121C - XT120D – XT121D
Two Stages Digital Controllers
with Multi Probe Input
1.
GENERAL WARNING
1.1
PLEASE READ BEFORE USING THIS MANUAL
•
This manual is part of the product and should be kept near the instrument for easy and quick reference.
•
The instrument shall not be used for purposes different from those described hereunder. It cannot be used
as a safety device.
•
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
•
Check the supply voltage is correct before connecting the instrument.
•
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
•
Warning: disconnect all electrical connections before any kind of maintenance.
•
The instrument must not be opened.
•
In case of failure or faulty operation send the instrument back to the distributor or to “ DIXELL S.p.A” (see
address) with a detailed description of the fault.
•
Consider the maximum current which can be applied to each relay (see Technical Data).
•
Ensure that the wires for probes, loads and the power supply are separated and far enough from each other,
without crossing or intertwining.
•
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
2.
GENERAL DESCRIPTION
The XT120C, XT121C and XT120D, XT121D (DIN RAIL format) are two-stage ON/OFF controllers for
temperature, humidity and pressure applications with direct or inverse action, user-selectable. The
analogue input type can be set by parameter between the following, according to the model:
-
PTC, NTC;
-
PTC, NTC, Pt100, Thermocouple J, K, S;
-
4÷20mA, 0÷1V, 0÷10V.
3.
FIRST INSTALLATION
3.1
PROBE SETTING
The pre-set probe type is written on the label of the instrument,
see picture. If it is different from the probe that has be used, set
the probe following procedure below
3.1.1 How to set the probe.
1.
Enter the programming menu by pressing the SET+
8
8
for 3s.
2.
Select the Pbc (Probe configuration) parameter and push the SET key.
3.
Set the kind of probe:
a.
Controller for temperature: Pt= Pt100, J = J thermocouple, c = K thermocouple, S = S
thermocouple; Ptc = PTC; ntc = ntc.
b.
Controller with current or voltage inputs: cur=4÷20mA, 0-1= 0÷1V, 10= 0÷10V
4.
Push the SET key to confirm it.
5.
Switch the controller off and on again.
NOTE: Before proceeding check and, if necessary; set with appropriate values the Minimum Set
Points (LS1 e LS2) and Maximum Set Points (US1 e US2). See also the paragraphs concerning
the programming.
4.
REGULATIONS
4.1
2 INDEPENDENT OUTPUTS (OUC=IND)
Two independent control stages (ouC=ind): output #1 at direct (S1C=dir) or inverse (S1C=in) action;
output #2 at (S2C = dir) direct or inverse (S2C =in) action.
E.I. with OUC = ind, S1C = dir (cooling), S2C = dir (cooling).
4.2
2 DEPENDENT OUTPUTS (OUC=DIP)
With dependent control stages (ouC=diP) SET2 is related to SET1:
therefore SET2 is: SET1+SET2
output #1 with direct or inverse action according to the S1C parameter; output #2 with direct or inverse
action according to the S2C.
E.I. with ouC=diP (dependent), S1C = dir (cooling), S2C = dir (cooling).
5.
FRONT PANEL COMMANDS
SET1: To display and modify target set
point1; in programming mode it
selects a parameter or confirm an
operation.
TO SWITCH THE INSTRUMENT
ON/OFF: If the function is enabled
(par. onF=yES), by pressing the
SET key for more than 4s the
controller is switched OFF. To
switch the instrument on again
press the SET key.
SET2: To display target set point2.
9
9
UP: in programming mode it browses
the parameter codes or increases
the displayed value. Hold it pressed
for a faster change
8
8
DOWN: in programming mode it
browses the parameter codes or
decreases the displayed value. Hold
it pressed for a faster change
KEY COMBINATIONS:
9
9
+
8
8
To lock & unlock the keyboard.
SET +
8
8
To enter in programming mode.
SET +
9
9
To return to the room temperature display.
5.1
USE OF LEDS
A series of light points on the front panels is used to monitor the loads controlled by the instrument.
Each LED function is described in the following table.
LED
MODE
FUNCTION
ON
Output 1 enabled
ON
Output 2 enabled
LED1 Flashing
- Programming Phase (flashing with LED2)
LED2 Flashing
- Programming Phase (flashing with LED1)
E.S.
ON
Energy saving activated by digital input
ON
- ALARM signal
- In “Pr2” indicates the parameter is also present in “Pr1”
5.2
TO SEE THE SETPOINT1 (OR SETPOINT2)
1.
Push and release the SET1 (SET2) key to see the Set point value;
2.
To come back to the normal display push again the SET1 (SET2) key or wait 10s.
5.3
TO CHANGE THE SETPOINT1 (OR SETPOINT2)
1.
Hold pushed for 2s the SET1 (SET2) key to change the Set point value;
2.
The value of the set point will be displayed and the LED1 & 2 start blinking;
3.
To change the Set value push the
9
9
or
8
8
arrows within 10s.
4.
To memorise the new set point value push the SET1 (SET2) key again or wait 10s.
5.4
TO ENTER THE PARAMETERS LIST “PR1
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1.
Push for 3s the SET1 + DOWN keys (LED1 & 2 start blinking).
2.
The controller will display the first parameter present in the Pr1 menu..
5.5
TO ENTER THE PARAMETERS LIST “PR2”
The “Pr2” parameter list contains the configuration parameters. A security code is required to enter it.
1.
Enter the “Pr1” level, see above paragraph.
2.
Select “Pr2” parameter and press the “SET1” key.
3.
The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
4.
Use
9
9
or
8
8
to input the security code in the flashing digit; confirm the figure by pressing “SET1”.
The security code is “321”.
5.
If the security code is correct the access to “Pr2” is enabled by pressing “SET1” on the last digit.