;7& ² ;7& ;7' ² ;7'
4/4
15.4
XT121C – 230V AC OR 115V AC
Hot-KEY
8(3)A250V
8(3)A250V
8(3)A250V
Line
LOAD 1 LOAD 2
Alarm
Input 4÷ 20m A
0÷ 1V / 0÷ 10V
PTC / N TC
Probe: Pt100=9–11 (10); Thermocouple J, K, S= 9(+) - 11(-)
115Vac supply: 7-8
15.5
XT120D – 230V AC OR 120V AC OR 24V AC
Input: 4÷ 20mA
0÷ 1V / 0÷ 10V
PTC
NTC
8(3)A250V
8(3)A250V
Line
LOAD 1
LOAD 2
H
o
t-K
E
Y
Analog
Out
Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-)
115Vac supply: 1-2; 24Vac supply: 1-2
15.6
XT121D – 230V AC OR 115V AC OR 24V AC
Input: 4÷ 20mA
0÷ 1V / 0÷ 10V
PTC
NTC
8(3)A250V
8(3)A250V
8(3)A250V
Line
LOAD 1
LOAD 2
Alarm
H
o
t-K
E
Y
Analog
Out
Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-)
115Vac supply: 1-2; 24Vac supply: 1-2
16.
DEFAULT SETTING VALUES
COD
Name
Range
°C/°F
Lev
Set1
Set point1
LS1÷US1
0/32
-
Set2
Set point2
LS2÷US2
1/34
-
Hy1
Differential 1
-Full Sc./ Full Sc.
-1/-2
Pr1
Hy2
Differential 1
-Full Sc./ Full Sc.
-1/-2
Pr1
LS1
Minimum set point1
Down Sc./ Set1
min
Pr2
LS2
Minimum set point2
Down Sc./ Set2
min
Pr2
US1
Maximum set point1
Set1/ Full Sc.
max
Pr2
US2
Maximum set point2
Set2/ Full Sc.
max
Pr2
ouC
Output configuration
ind= independent; diP = dependent
ind
Pr2
S1C
Action type output 1
in= Inverse; dir=direct
in
Pr2
S2C
Action type output 2
in= Inverse; dir=direct
in
Pr2
Ac
Anti-short cycle delay:
0÷250 sec
0
Pr2
on
Minimum time a stage stays switched
ON
0÷250 sec
0
Pr2
ono
Minimum time between 2 following
switching ON of the same load
0÷120 min
0
Pr2
ALC
Alarm configuration
rE=relat.; Ab= absolute
rE
Pr2
ALL
Minumum alarm (ALC=rE)
(ALC=Ab)
0 ÷ |Start Sc.-Set1|;
Start Sc.÷ ALu
10.0/ 20 Pr2
ALU
Maximum alarm (ALC=rE)
(ALC=Ab)
0 ÷ |Full Sc.-Set1|.
ALL÷ Full Scale
10.0/ 20 Pr2
ALH
Alarm recovery differential
0÷Full scale
2.0/4
Pr2
ALd
Alarm delay
0÷999 min
15
Pr2
dAO
Alarm delay at start up
0÷23h 50min
1.3
Pr2
So1
Out1 status with faulty pr.
oFF=open on=closed
oFF
Pr2
So2
Out2 status with faulty pr.
oFF=open on=closed
oFF
Pr2
tbA
1
Alarm relay disabling
no; yES
yES
Pr2
AS
1
Alarm relay polarity
CL÷oP
oP
Pr2
Lci
2
Start scale with current or voltage input
-1999÷1999
various
Pr1
Uci
2
End scale with current or voltage input
-1999÷1999
various
Pr1
OPb
Probe calibration
-Full Sc./ Full Sc.
0.0
Pr1
rES
Resolution
in=NO; dE=0,1; cE=0,01
in
Pr2
UdM
Measurement unit (temp.)
(current/voltage)
°C=°C; °F= °F;
0=°C; 1=°F; 2=RH; 3=bar; 4=PSI,
5=off
various
Pr1
PbC
Kind of probe
Pt=Pt100; J=tcJ; c= tck; S=tcS;
Ptc=PTC; ntc= NTC; 0-1=0÷1V; 10=
0÷10V; cur=0÷20mA
various
Pr1
P3F
3
rd
wire presence
no=2 wires; yES=3 wires
no
Pr2
Aoc
3
Analog output configuration
Pb = probe; Er = Probe-Set1
Pb
Pr2
LAo
3
Lower An.Output limit
Down Sc
various
Pr2
uAo
3
Upper An. Output limit
Full sc.
various
Pr2
SAo
3
Analog output safety
on; oFF
oFF
Pr2
HES
Energy saving differential
Down Sc./ Full Sc.
0.0
Pr2
i1F
Digital input configuration
c-H / oFF / AuS / HES / EAL / bAL
EAL
Pr2
i1P
Digital input polarity
cL=closing; oP=opening
cL
Pr2
did
Alarm delay for dig. input
0÷120m
0
Pr2
Adr
Serial address
RS485 address
1
Pr2
OnF
oFF function enabling
no=not enabled; oFF=enabled
no
Pr2
Ptb
Parameter table
Readable only
--
Pr2
rEL
Software release
Readable only
---
Pr2
Pr2
To access the Pr2
Readable only
321
Pr1
1
Only for XT121C/XT121D;
2
Only for instrument with 4÷20mA or 0÷1V or 0÷10V
3
Only for instrument analog output
Dixell S.p.A. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY