;7& ² ;7&  ;7' ² ;7'

4/4

15.4

 

XT121C – 230V AC OR 115V AC

       

   

Hot-KEY

8(3)A250V

8(3)A250V

8(3)A250V

Line

LOAD 1 LOAD 2

Alarm

Input 4÷ 20m A

0÷ 1V  / 0÷ 10V 

   

PTC   /  N TC

Probe: Pt100=9–11 (10); Thermocouple J, K, S= 9(+) - 11(-)
115Vac supply: 7-8

15.5

 

XT120D – 230V AC OR 120V AC OR 24V AC

Input: 4÷ 20mA 

0÷ 1V  / 0÷ 10V 

  

PTC 

NTC

8(3)A250V

8(3)A250V

Line

LOAD 1

LOAD 2

H

o

t-K

E

Y

Analog

Out

Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-)
115Vac supply: 1-2;  24Vac supply: 1-2

15.6

 

XT121D – 230V AC OR 115V AC OR 24V AC

Input: 4÷ 20mA 

0÷ 1V  / 0÷ 10V 

  

PTC 

NTC

8(3)A250V

8(3)A250V

8(3)A250V

Line

LOAD 1

LOAD 2

Alarm

H

o

t-K

E

Y

Analog

Out

Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-)
115Vac supply: 1-2;  24Vac supply: 1-2

16.

 

DEFAULT SETTING VALUES

COD

Name

Range

°C/°F

Lev

Set1

Set point1

LS1÷US1

0/32

-

Set2

Set point2

LS2÷US2

1/34

-

Hy1

Differential 1

-Full Sc./ Full Sc.

-1/-2

Pr1

Hy2

Differential 1

-Full Sc./ Full Sc.

-1/-2

Pr1

LS1

Minimum set point1

Down Sc./ Set1

min

Pr2

LS2

Minimum set point2

Down Sc./ Set2

min

Pr2

US1

Maximum set point1

Set1/ Full Sc.

max

Pr2

US2

Maximum set point2

Set2/ Full Sc.

max

Pr2

ouC

Output configuration

ind= independent;  diP = dependent

ind

Pr2

S1C

Action type output 1

in= Inverse; dir=direct

in

Pr2

S2C

Action type output 2

in= Inverse; dir=direct

in

Pr2

Ac

Anti-short cycle delay:

0÷250 sec

0

Pr2

on

Minimum time a stage stays switched
ON

0÷250 sec

0

Pr2

ono

Minimum time between 2 following
switching ON of the same load

0÷120 min

0

Pr2

ALC

Alarm configuration

rE=relat.; Ab= absolute

rE

Pr2

ALL

Minumum alarm (ALC=rE)
                         (ALC=Ab)

0 ÷ |Start Sc.-Set1|;
Start Sc.÷ ALu

10.0/ 20 Pr2

ALU

Maximum alarm (ALC=rE)
                          (ALC=Ab)

0 ÷ |Full Sc.-Set1|.
ALL÷ Full Scale

10.0/ 20 Pr2

ALH

Alarm recovery differential

0÷Full scale

2.0/4

Pr2

ALd

Alarm delay

0÷999 min

15

Pr2

dAO

Alarm delay at start up

0÷23h 50min

1.3

Pr2

So1

Out1 status with faulty pr.

oFF=open  on=closed

oFF

Pr2

So2

Out2 status with faulty pr.

oFF=open  on=closed

oFF

Pr2

tbA

1

Alarm relay disabling

no; yES

yES

Pr2

AS

1

Alarm relay polarity

CL÷oP

oP

Pr2

Lci

2

Start scale with current or voltage input

-1999÷1999

various

Pr1

Uci

2

End scale with current or voltage input

-1999÷1999

various

Pr1

OPb

Probe calibration

-Full Sc./ Full Sc.

0.0

Pr1

rES

Resolution

in=NO; dE=0,1; cE=0,01

in

Pr2

UdM

Measurement unit (temp.)
        (current/voltage)

°C=°C; °F= °F;
0=°C; 1=°F; 2=RH; 3=bar; 4=PSI,
5=off

various

Pr1

PbC

Kind of probe

Pt=Pt100; J=tcJ; c= tck; S=tcS;
Ptc=PTC; ntc= NTC; 0-1=0÷1V; 10=
0÷10V; cur=0÷20mA

various

Pr1

P3F

3

rd

 wire presence

no=2 wires; yES=3 wires

no

Pr2

Aoc

3

Analog output configuration

Pb = probe; Er = Probe-Set1

Pb

Pr2

LAo

3

Lower An.Output limit

Down Sc

various

Pr2

uAo

3

Upper An. Output limit

Full sc.

various

Pr2

SAo

3

Analog output safety

on; oFF

oFF

Pr2

HES

Energy saving differential

Down Sc./ Full Sc.

0.0

Pr2

i1F

Digital input configuration

c-H / oFF / AuS / HES / EAL / bAL

EAL

Pr2

i1P

Digital input polarity

cL=closing; oP=opening

cL

Pr2

did

Alarm delay for dig. input

0÷120m

0

Pr2

Adr

Serial address

RS485 address

1

Pr2

OnF

oFF function enabling

no=not enabled; oFF=enabled

no

Pr2

Ptb

Parameter table

Readable only

--

Pr2

rEL

Software release

Readable only

---

Pr2

Pr2

To access the Pr2

Readable only

321

Pr1

Only for XT121C/XT121D;

2

 Only for instrument with 4÷20mA or 0÷1V or 0÷10V

3

 Only for instrument analog output

Dixell S.p.A.  Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13

(PDLO GL[HOO#GL[HOOFRP  KWWSZZZGL[HOOFRP

Summary of Contents for XT120C

Page 1: ...r inverse S1C in action output 2 at S2C dir direct or inverse S2C in action E I with OUC ind S1C dir cooling S2C dir cooling 4 2 2 DEPENDENT OUTPUTS OUC DIP With dependent control stages ouC diP SET2 is related to SET1 therefore SET2 is SET1 SET2 output 1 with direct or inverse action according to the S1C parameter output 2 with direct or inverse action according to the S2C E I with ouC diP depend...

Page 2: ...Y LCI Start of scale only with current or voltage input with rES in dE cE 99 00 199 00 with rES irE 999 1999 Adjustment of read out corresponding to 4mA or 0V input signal UCI End of scale only with current or voltage input with rES in dE cE 99 00 199 00 with rES irE 999 1999 Adjustment of read out corresponding to 20mA or 1V or 10V input signal oPb Probe calibration 999 999 allows to adjust possi...

Page 3: ...vely HA Maximum temperature alarm Alarm output ON Other outputs unchanged LA Minimum temperature alarm Alarm output ON Other outputs unchanged EAL External alarm Output unchanged bAL Serious external alarm Output OFF 13 1 ALARM RELAY STATUS Status of the instrument XT121C XT121D AS CL AS oP AS CL AS oP Instrument off 5 6 closed 5 6 closed 23 24 closed 23 24 closed Normal operating 5 6 closed 5 6 o...

Page 4: ... Pr2 ALU Maximum alarm ALC rE ALC Ab 0 Full Sc Set1 ALL Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 So1 Out1 status with faulty pr oFF open on closed oFF Pr2 So2 Out2 status with faulty pr oFF open on closed oFF Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL...

Reviews: