UR SERIES – COMMUNICATIONS GUIDE
SCL LOG MESSAGES
CHAPTER 3: IEC 61850 COMMUNICATION
3
check_goose_publishing: iedName or apName missing
This message is logged when the iedName or apName is missing from the GOOSE publisher IED.
check_goose_publishing: gcb <gcb name> must be configured in Master/LLN0
This message is logged when the GOOSE control block is not configured in Master/LLN0.
check_goose_publishing: too many GSEControl
This message is logged when the number of GSEControl are more than the eight supported.
check_goose_publishing: wrong name gcbName=<gcb name>
This message is logged when the index of GoCB is beyond 07.
check_goose_publishing: NO GSE=<gcb name> found
This message is logged when the mentioned GSE element is not found.
check_goose_publishing: NO DataSet=<gcb datSet> found
This message is logged when the publisher dataset cannot be found.
check_iec_report: iedName or apName missing
This message is logged when validating the report control or dataset and the iedName or apName cannot be found.
check_iec_report: rcb <report control block name> must be configured in Master/LLN0
This message is logged when a report control is detected in a node other than Master/LLN0.
check_iec_report: too many buffered ReportControl
This message is logged when the number of buffered report controls is more than 20.
check_iec_report: too many unbuffered ReportControl
This message is logged when the number of unbuffered report controls is more than 14.
check_iec_report: RptEnabled max=<maximum number of supported clients>, too many clients
This message is logged when more than one client is requesting the report to be enabled.
check_iec_report: too many DataSet(<number of datasets>) used by report
This message is logged when more than four datasets are used by report controls.
UR7.30 and above only supports SCL edition 2
This message is logged when the edition information in the CID file says edition 1 of IEC 61850.
CID validation FAILED
This message is logged when the CID file validation fails.
Parsing Failed <Timestamp>
This message is logged when parsing fails.
Missing configurable DAIs in LN <logical node prefix><lnClass> in LD <ldinst>
This message is logged if a configurable instantiated data attribute (DAI), that is not a "d" attribute, is missing from the new
CID file.
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...