CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-39
2
"
3412
Neutral Current Unbalance Apply Angle
0 to 1
---
1
F126
0 (No)
"
3413
Neutral Current Unbalance Apply
Magnitude Actual Value (Read Only)
0 to 0.1500
---
0.000
1
F003
0
"
3415
Neutral Current Unbalance Apply Angle
Actual Value (Read Only)
0 to 359
degrees 1
F003
0
"
3417
...Repeated for Neutral Current Unbalance
2
"
341E
...Repeated for Neutral Current Unbalance
3
Neutral Voltage Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 Modules)
C70
3430
Neutral Voltage Unbalance Automatic
Setting Function
0 to 2
---
1
F092
0 (Disabled)
"
3431
59NU XA/XB Ratio Actual Value (Read Only) 0 to 9.9999
---
0.000
1
F003
0
"
3433
Neutral Voltage Unbalance Auto-set XA/XB
Ratio
0 to 1
---
1
F126
0 (No)
"
3434
59NU XA/XC Ratio Actual Value (Read Only) 0 to 9.9999
---
0.000
1
F003
0
"
3436
Neutral Voltage Unbalance Auto-set XA/XC
Ratio
0 to 1
---
1
F126
0 (No)
"
3437
...Repeated for Neutral Voltage Unbalance
2
"
343E
...Repeated for Neutral Voltage Unbalance
3
Phase Current Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 Modules)
C70
3450
Phase Current Unbalance Automatic
Setting Function
0 to 2
---
1
F092
0 (Disabled)
"
3451
Phase Current Unbalance Ka Actual Value
(Read Only)
–0.1000 to 0.1000
---
0.000
1
F004
0
"
3453
Phase Current Unbalance Auto-set Ka
0 to 1
---
1
F126
0 (No)
"
3454
Phase Current Unbalance Kb Actual Value
(Read Only)
–0.1000 to 0.1000
---
0.000
1
F004
0
"
3456
Phase Current Unbalance Auto-set Kb
0 to 1
---
1
F126
0 (No)
"
3457
Phase Current Unbalance Kc Actual Value
(Read Only)
–0.1000 to 0.1000
---
0.000
1
F004
0
"
3459
Phase Current Unbalance Auto-set Kc
0 to 1
---
1
F126
0 (No)
"
345A
...Repeated for Phase Current Unbalance 2
"
3464
...Repeated for Phase Current Unbalance 3
Voltage Differential Commands and Actual Values (Read/Write Unless Noted) (3 Modules)
C70
3470
Voltage Differential Automatic Setting
Function
0 to 2
---
1
F092
0 (Disabled)
"
3471
Voltage Differential Ka Actual Value (Read
Only)
0 to 99.9999
---
0.000
1
F003
0
"
3473
Voltage Differential Auto-set Ka
0 to 1
---
1
F126
0 (No)
"
3474
Voltage Differential Kb Actual value (Read
Only)
0 to 99.9999
---
0.000
1
F003
0
"
3476
Voltage Differential Auto-set Kb
0 to 1
---
1
F126
0 (No)
"
3477
Voltage Differential Kc Actual Value (Read
Only)
0 to 99.9999
---
0.000
1
F003
0
"
3479
Voltage Differential Auto-set Kc
0 to 1
---
1
F126
0 (No)
"
347A
...Repeated for Voltage Differential 2
"
3484
...Repeated for Voltage Differential 3
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...