2-108
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
Field Ground (Read/Write Grouped Setting)
G60
7E7E
Field Ground Function
0 to 1
---
1
F102
0 (Disabled)
"
7E7F
Field Ground Injection Frequency
0.1 to 3
Hz
0.01
F001
100
"
7E80
Field Ground Injection Connection Type
0 to 1
---
1
F613
0 (Single
Point)
"
7E81
Field Ground STG1 Pickup
1 to 500
kOhm
1
F001
20
"
7E82
Field Ground STG1 Delay
0.1 to 600
seconds 0.1
F001
100
"
7E83
Field Ground STG2 Pickup
1 to 500
kOhm
1
F001
5
"
7E84
Field Ground STG2 Delay
0.1 to 600
seconds 0.1
F001
30
"
7E85
Field Ground UC Pickup
0.05 to 100
mA
0.01
F001
100
"
7E86
Field Ground UC Delay
0.1 to 600
seconds 0.01
F001
100
"
7E87
Field Ground Block
0 to 4294967295
---
1
F300
0
"
7E89
Field Ground Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E8A
Field Ground Events
0 to 1
---
1
F102
0 (Disabled)
Distance (Read/Write Grouped Setting)
D30, D60, G60,
L60, L90, T60
7E8C
Distance Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
7E8D
Memory Duration
5 to 25
cycles
1
F001
10
"
7E8E
Force Self-Polarization
0 to 4294967295
---
1
F300
0
"
7E90
Force Memory Polarization
0 to 4294967295
---
1
F300
0
Distance Actual Values (Read Only)
D30, D60, G60,
L60, L90, T60
7E94
AB Loop Resistance
-2147483647 to
2147483647
ohm
1
F060
0
"
7E96
AB Loop Reactance
-2147483647 to
2147483647
ohm
1
F060
0
"
7E98
AB Loop Impedance Magnitude
0 to 2147483647
ohm
1
F060
0
"
7E9A
AB Loop Impedance Angle
-359.9 to 0
degrees 0.1
F002
0
"
7E9B
BC Loop Resistance
-2147483647 to
2147483647
ohm
1
F060
0
"
7E9D
BC Loop Reactance
-2147483647 to
2147483647
ohm
1
F060
0
"
7E9F
BC Loop Impedance Magnitude
0 to 2147483647
ohm
1
F060
0
"
7EA1
BC Loop Impedance Angle
-359.9 to 0
degrees 0.1
F002
0
"
7EA2
CA Loop Resistance
-2147483647 to
2147483647
ohm
1
F060
0
"
7EA4
CA Loop Reactance
-2147483647 to
2147483647
ohm
1
F060
0
"
7EA6
CA Loop Impedance Magnitude
0 to 2147483647
ohm
1
F060
0
"
7EA8
CA Loop Impedance Angle
-359.9 to 0
degrees 0.1
F002
0
"
7EA9
AG Loop Resistance
-2147483647 to
2147483647
ohm
1
F060
0
"
7EAB
AG Loop Reactance
-2147483647 to
2147483647
ohm
1
F060
0
"
7EAD
AG Loop Impedance Magnitude
0 to 2147483647
ohm
1
F060
0
"
7EAF
AG Loop Impedance Angle
-359.9 to 0
degrees 0.1
F002
0
"
7EB0
BG Loop Resistance
-2147483647 to
2147483647
ohm
1
F060
0
"
7EB2
BG Loop Reactance
-2147483647 to
2147483647
ohm
1
F060
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...