3-126
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6.7 Non-volatile latches (NVLat)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-115: Non-volatile latch data objects
3.5.6.8 Oscillography (Osc)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-116: Oscillograph data objects
stVal
BOOLEAN
ST VO
ξ
On
R
Id
ξ
VSG
This setting is used to describe virtual
output
ξ
R
setVal
VISIBLE
STRING255
SP The first twelve characters are
mapped to setting VIRTUAL
OUTPUT
ξ
ID
R
LNName:
NVLatGAPC#
LDevice inst:
Gen
UR element:
Non-Volatile Latches element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind1
SPS
LATCH # ON operand value
R
stVal
BOOLEAN
ST LATCH # ON
R
Ind2
SPS
”LATCH # OFF operand value
R
stVal
BOOLEAN
ST LATCH # OFF
R
InRef1
ORG
Non-Volatile Latch LATCH # SET setting
R
setSrcRef
ObjectReference
SP Non-Volatile Latch SET setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
Non-Volatile Latch LATCH # RESET setting
R
setSrcRef
ObjectReference
SP Non-Volatile Latch RESET setting Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
OscRDRE1
LDevice inst:
Gen
UR element:
Oscillography, core logical node
data obj. data attribute
Type
FC UR Name
Description
R/W/C
RcdMade
SPS
Records are available
R
stVal
BOOLEAN
ST
R
FltNum
INS
NUMBER OF TRIGGERS actual value
R
stVal
INT32
ST NUMBER OF TRIGGERS actual
value
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
NumCycPe
r
INS
CYCLES PER RECORD actual value
R
stVal
INT32
ST Actual value CYCLES PER RECORD
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
RsTms
INS
LAST CLEARED DATE actual value
R
stVal
INT32
ST Actual value LAST CLEARED DATE
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
4, the code for time
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
RcdTrg
SPC
External command to trigger recorder
R/Ctrl
LNName:
FlxLgcGAPC1
LDevice inst:
Gen
UR element:
FlexLogic
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...