CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-123
3
3.5.6.3 Digital counters (DigCnt)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-111: Digital counter data objects
stVal
INT32
ST
0 if data logger is cleared, 1 once a sample
has been recorded.
R
RcdMade
SPS
Recording started, timestamp mapped to
NEWEST SAMPLE TIME actual
R
stVal
BOOLEAN
ST Transitions to true whenever a
new sample is recorded, cleared
to false when recorder is cleared
R
MemClr
SPC
Clear all data logger records command
R/Ctrl
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
2 ms (actually one pass)
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF DatLogRDRE1.MemClr.ctlModel
R/W/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
InRef1
ORG
DATA LOGGER TRIGGER setting.
R
setSrcRef
ObjectReference
SP DATA LOGGER TRIGGER setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
DigCntFCNT#
LDevice inst:
Gen
UR element:
Digital Counters #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
HiLim
SPS
Counter #(CNT#) HI, which indicates the
number of pulses counted is above the set
number
R
stVal
BOOLEAN
ST Counter #(CNT#) HI
R
EqLim
SPS
Counter #(CNT#) EQL operand, which
indicates the number of pulses counted is
equal to the set numbe
R
stVal
BOOLEAN
ST Counter #(CNT#) EQL
R
LoLim
SPS
Counter #(CNT#) LO operand, which
indicates the number of pulses counted is
below the set number
R
stVal
BOOLEAN
ST Counter #(CNT#) LO
R
CntRs
BCR
Counter # ACCUM, which indicates the
accumulated number of pulses
R
actVal
INT64
ST actual value of Counter # ACCUM
R
frVal
INT64
ST actual value of Counter # FROZEN
(count)
R
frTm
TimeStamp
ST actual value of Counter # FROZEN
(date/time) combined with
Counter # MICROS (fractional
seconds)
R
units.SIUnit
ENUMERATED
COUNTER # UNITS
R
units.multiplier
ENUMERATED
COUNTER # UNITS
R
pulsQty
FLOAT32
CF
1
R
LNName:
DatLogRDRE1
LDevice inst:
Gen
UR element:
Data Logger
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...