2-106
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
Motor Acceleration Time (Read/Write Grouped Setting)
M60
7B40
Motor Acceleration Function
0 to 1
---
1
F102
0 (Disabled)
"
7B41
Motor Acceleration Current
1.00 to 10.00
×
FLA
0.01
F001
600
"
7B42
Motor Acceleration Time
0.05 to 180.00
s
0.01
F001
1000
"
7B43
Motor Acceleration Mode
0 to 1
---
1
F097
0 (Definite
Time)
"
7B44
Motor Acceleration Block
0 to 4294967295
---
1
F300
0
"
7B46
Motor Acceleration Target
0 to 2
---
1
F109
0 (Self-reset)
"
7B47
Motor Acceleration Events
0 to 1
---
1
F102
0 (Disabled)
"
7B48
Speed 2 Motor Acceleration Current
1.00 to 10.00
x FLA
0.01
F001
600
"
7B49
Speed 2 Motor Acceleration Time
0.05 to 180.00
s
0.01
F001
1000
"
7B4A
Speed 2 Motor Acceleration Mode
0 to 1
---
1
F097
0 (Definite
Time)
"
7B4B
Speed 2 Motor Acceleration Speed 1-2
0.05 to 180.00
s
0.01
F001
1000
"
7B4C
Speed 2 Motor Acceleration Block
0 to 4294967295
---
1
F300
0
"
7B4E
Reserved (9 items)
---
---
---
F001
0
User Programmable Pushbuttons (Read/Write Setting) (16 Modules)
All
7B60
User Programmable Pushbutton 1 Function 0 to 2
---
1
F137
0 (Disabled)
"
7B61
User Programmable Pushbutton 1 Top Line ---
---
---
F202
(none)
"
7B6B
User Programmable Pushbutton 1 On Text ---
---
---
F202
(none)
"
7B75
User Programmable Pushbutton 1 Off Text ---
---
---
F202
(none)
"
7B7F
User Programmable Pushbutton 1 Drop-
Out Time
0 to 60
s
0.05
F001
0
"
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
7B82
User Programmable Pushbutton 1 LED
Operand
0 to 4294967295
---
1
F300
0
"
7B84
User Programmable Pushbutton 1
Autoreset Delay
0.2 to 600
s
0.1
F001
10
"
7B85
User Programmable Pushbutton 1
Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
"
7B86
User Programmable Pushbutton 1 Local
Lock Operand
0 to 4294967295
---
1
F300
0
"
7B88
User Programmable Pushbutton 1
Message Priority
0 to 2
---
1
F220
0 (Disabled)
"
7B89
User Programmable Pushbutton 1 Remote
Lock Operand
0 to 4294967295
---
1
F300
0
"
7B8B
User Programmable Pushbutton 1 Reset
Operand
0 to 4294967295
---
1
F300
0
"
7B8D
User Programmable Pushbutton 1 Set
Operand
0 to 4294967295
---
1
F300
0
"
7B8F
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
"
7B90
...Repeated for User Programmable
Pushbutton 2
"
7BC0
...Repeated for User Programmable
Pushbutton 3
"
7BF0
...Repeated for User Programmable
Pushbutton 4
"
7C20
...Repeated for User Programmable
Pushbutton 5
"
7C50
...Repeated for User Programmable
Pushbutton 6
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...