CHAPTER 3: IEC 61850 COMMUNICATION
SCL LOG MESSAGES
UR SERIES – COMMUNICATIONS GUIDE
3-161
3
No DAType=<new data attribute type> found for DA=<data attribute> in new IED
The DAType of the specified data attribute in the new CID file is missing.
No DAType=<new data attribute type> found for DA=<data attribute> in existing IED
The DAType of the specified data attribute in the existing CID file is missing.
DAType=<new data attribute type> is different in new IED
The DAType is different in the new CID file from the reference in the device.
No EnumType=<enumeration type> found in new IED
The EnumType is missing in the new CID file.
No EnumType=<enumeration type> found in existing IED
The EnumType is missing in the existing CID file.
EnumType=<enumeration type> is different in existing IED
The EnumType is different in the new CID from the reference in the device.
DA=<data attribute> is DOType=<data object type> mismatch
The data attribute in the DOType differs from the reference in the device.
New DAType=<data attribute type> has different number of BDA
The DAType in the new CID file has a different number of BDA when compared to the reference in the device.
No BDA=<base data attribute> found in DAType=<data attribute type> in the new IED
The base data attributes are missing the specified DAType in the new CID file.
No DAType=<data attribute type> for BDA=<base data attribute> in new IED
The data attribute type is missing for the base data attribute in the new CID file.
No DAType=<data attribute type> for BDA=<base data attribute> in existing IED
The data attribute type is missing for the base data attribute in the existing CID file.
DAType=<data attribute type> is different in new IED
The data attribute type is different in the new CID file from the reference in the device.
No EnumType=<enumeration type> is found in new IED
The enumeration type is missing in the new CID file.
No EnumType=<enumeration type> is found in existing IED
The enumeration type is missing in the existing CID file.
EnumType=<enumeration type> is different in new IED
The enumeration type in the new CID file differs from the reference in the device.
CID is invalid, restored backup CID copy. Manually reboot the relay to initialize with backup CID.
The working copy of the CID file is invalid, hence the backup copy is ready to be used. To activate the configuration from
the backup copy, a reboot is required.
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...