![background image](http://html1.mh-extra.com/html/ge/ur-series/ur-series_manual_4212129305.webp)
CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-89
3
3.5.4.4 Breaker control (Bkr)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-90: Breaker control data objects
Table 3-91: Breaker control data objects
IsoBlk
ACT
ISOLATOR # BLOCK OP operand
R
general
BOOLEAN
ST ISOLATOR # BLOCK
R
InRef1
ORG
ISOLATOR # OPEN setting
R
setSrcRef
ObjectReference
SP ISOLATOR # OPEN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
ISOLATOR # CLOSED setting
R
setSrcRef
ObjectReference
SP ISOLATOR # CLOSED
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef3
ORG
ISOLATOR # RESET setting
R
setSrcRef
ObjectReference
SP ISOLATOR # RESET
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
BkrCSWI#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Pos
DPC
Breaker position control and status
R/Ctrl
stVal
CODED ENUM
ST Bkr0XCBR#.Pos.stVal
R
stSeld
BOOLEAN
ST
The controllable data status is “selected”
R
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
2 ms (actually one pass)
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF BkrCSWI# Pos ctlModel
R/W/C
sboTimeout
INT32U
CF BkrCSWI# Pos sboTimeout
R/W/C
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF BkrCSWI# Pos operTimeout
R/C
LNName:
BkrCILO#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
EnaOpn
SPS
Enable Open status
R
stVal
BOOLEAN
ST
The state of the operand selected by setting
XCBR# INTERLOCK OPN
R
EnaCls
SPS
Enable Close status
R
stVal
BOOLEAN
ST
Logical OR of the state of the operand
selected by setting XCBR# SYNCCHECK CLS
and the state of the operand selected by
setting XCBR# INTERLOCK CLS
R
InRef2
ORG
XCBR# INTERLOCK OPN setting.
R
setSrcRef
ObjectReference
SP XCBR# INTERLOCK OPN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef3
ORG
XCBR# INTERLOCK CLS setting.
R
setSrcRef
ObjectReference
SP XCBR# INTERLOCK CLS
Reference to the data attribute to input
R/C
LNName:
B_IsoSSWI#
LDevice inst:
System
UR element:
B90 ISOLATOR # function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...