3-68
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.41 Phase undervoltage (PhsUv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-62: Phase undervoltage data objects
3.5.2.42 Power swing detection (RPSB_)
This element is instantiated in the following products: D30, D60, G60, L60, L90, N60, T60.
Table 3-63: Power swing detection data objects
LNName:
PhsUvPTUV#
LDevice inst:
Prot
UR element:
Phase Undervoltage element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE UV# PKP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE UV# PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional.
R
phsA
BOOLEAN
ST PHASE UV# PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional.
R
phsB
BOOLEAN
ST PHASE UV# PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional.
R
phsC
BOOLEAN
ST PHASE UV# PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional.
R
Op
ACT
PHASE UV# OP operand (including
individual three phases)
R
general
BOOLEAN
ST PHASE UV# OP
R
phsA
BOOLEAN
ST PHASE UV# OP A
R
phsB
BOOLEAN
ST PHASE UV# OP B
R
phsC
BOOLEAN
ST PHASE UV# OP C
R
Dpo
SPS
PHASE UV# DPO operand, which is the
inverse of PHASE UV PKP
R
stVal
BOOLEAN
ST PHASE UV# DPO
R
DpoPhs
β
SPS
PHASE UV# DPO
β
operands” (where
β
refers to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE UV# DPO
β
(where
β
refers
to Phase-A, B or C)
R
BlkRef
γ
ORG
PHASE UV# BLOCK setting for setting group
γ
R
setSrcRef
ObjectReference
SP PHASE UV# BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PwrSwgRPSB1
LDevice inst:
Prot
UR element:
Power Swing Detect element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
POWER SWING INCOMING operand
R
general
BOOLEAN
ST POWER SWING INCOMING
R
dirGeneral
ENUMERATED
ST
0
R
StrOutgoin
g
SPS
POWER SWING OUTGOING operand
R
stVal
BOOLEAN
ST POWER SWING OUTGOING
R
Op
ACT
POWER SWING TRIP
R
general
BOOLEAN
ST POWER SWING TRIP
R
BlkZn
SPS
POWER SWING BLOCK operand
R
stVal
BOOLEAN
ST POWER SWING BLOCK
R
Z1Chr1
SPS
POWER SWING OUTER operand
R
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...