3-118
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
ClcMth
ENG
Calculation method of statistical data
objects
R
setVal
ENUMERATED
SP UNSPECIFIED
R
InSyn
ORG
Only instantiated in DmdMtrMMTR1
R
setSrcRef
ObjectReference
SP DEMAND TRIGGER
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
RsStat
SPC
Only instantiated in DmdMtrMMTR1. Clears
demand for all sources.
R/Ctrl
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
0 indicates the duration is locally defined
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF DmdMtrMMTR1.RsStat.ctlModel
R/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
AaDmd
MV
SRC # DMD IA, in primary amperes
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # DMD IA
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF DmdMtrMMTR#.AaDmd.db
R/C
zeroDb
INT32U
CF
Current cut-off level
R
AaMaxDm
dDt
MV
SRC # DMD IA MAX, in primary amperes
with associated date, SRC # DMD IA DATE
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # DMD IA MAX
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF DmdMtrMMTR#.AaMaxDmdDt.db
R/C
zeroDb
INT32U
CF
Current cut-off level
R
AbDmd
MV
SRC # DMD IB, in primary amperes
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # DMD IB
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF DmdMtrMMTR#.AbDmd.db
R/C
zeroDb
INT32U
CF
Current cut-off level
R
LNName:
DmdMtrMMTR#
LDevice inst:
Meter
UR element:
Signal Source # NAME Demand Metering
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...