CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-111
3
phsC.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsC.units
Unit
CF
R
phsC.units.SIUnit ENUMERATED
63, the code for primary volt amperes
reactive (VIsin
Θ
)
R
phsC.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsC.db
INT32U
CF MMXU# VAr.phsC DEADBAND
R/W/C
phsC.zeroDb
INT32U
CF
Power cut-off level
R
A
VA
WYE
SRC # Phase Apparent Power, in primary
VA
R
phsA
CMV
R
phsA.instCVal
Vector
MX
R
phsA.instCVal.ma
g
.f
FLOAT32
SRC # Phase A Apparent Power
R
phsA.cVal
Vector
MX
R
phsA.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsA.units
Unit
CF
R
phsA.units.SIUnit ENUMERATED
61, the code for primary volt amperes
(VA)
R
phsA.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsA.db
INT32U
CF MMXU# VA.phsA DEADBAND
R/W/C
phsA.zeroDb
INT32U
CF
Power cut-off level
R
phsB
CMV
R
phsB.instCVal
Vector
MX
R
phsB.instCVal.ma
g
.f
FLOAT32
SRC # Phase B Apparent Power
R
phsB.cVal
Vector
MX
R
phsB.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsB.units
Unit
CF
R
phsB.units.SIUnit ENUMERATED
61, the code for primary volt amperes
(VA)
R
phsB.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsB.db
INT32U
CF MMXU# VA.phsB DEADBAND
R/W/C
phsB.zeroDb
INT32U
CF
Power cut-off level
R
phsC
CMV
R
phsC.instCVal
Vector
MX
R
phsC.instCVal.ma
g
.f
FLOAT32
SRC # Phase C Apparent Power
R
phsC.cVal
Vector
MX
R
phsC.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
phsC.units
Unit
CF
R
phsC.units.SIUnit ENUMERATED
61, the code for primary volt amperes
(VA)
R
phsC.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phsC.db
INT32U
CF MMXU# VA.phsC DEADBAND
R/W/C
LNName: ACsrcMMXU#
LDevice inst: Meter
UR element: AC Source #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...