CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-121
3
3.5.5.5 Energy metering (EnrMtr)
This element is instantiated in the following products: C60, D60, F35, F60, G30, G60, L90, M60, N60, T60.
Table 3-108: Energy metering data objects
LNName:
EnrMtrMMTR#
LDevice inst:
Meter
UR element:
Signal Source # Energy Metering
data obj. data attribute
Type
FC UR Name
Description
R/W/C
PosTotWh
MV
SRC # Total Watt-hour in positive direction
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # POS WATTHOUR
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
72, the code for real energy in watt hours
(Wh)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF EnrMtrMMTR#.PosTotWh.db
R/W/C
NegTotWh
MV
SRC # Total Watt-hour in negative direction
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # NEG WATTHOUR
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
72, the code for real energy in watt hours
(Wh)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF EnrMtrMMTR#.NegTotWh.db
R/W/C
PosTotVArh
MV
SRC # Total VAr-hour in positive direction
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # T POS VARHOUR
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
73, the code for reactive energy in volt
ampere hours (VArh)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF EnrMtrMMTR#.PosTotVArh.db
R/W/C
NegTotVAr
h
MV
SRC # Total VAr-hour in negative direction
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # NEG VARHOUR
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
73, the code for reactive energy in volt
ampere hours (VArh)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF EnrMtrMMTR#.NegTotVArh.db
R/W/C
RsStat
SPC
Only instantiated in EnrMtrMMTR1
R/Ctrl
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
0 indicates the duration is locally defined
R
pulseConfig
.offDur
INT32U
0
R
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...