3-56
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-42: Line current differential local terminal current data objects
setSrcRef
ObjectReference
SP BLOCK GPS TIME REF setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef
γ
ORG
CURRENT DIFF BLOCK setting of setting
group
γ
R
setSrcRef
ObjectReference
SP CURRENT DIFF BLOCK setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
05
ORG
CURRENT DIFF KEY DTT setting of setting
group
γ
R
setSrcRef
ObjectReference
SP CURRENT DIFF KEY DTT setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
06
ORG
STUB BUS DISCONNECT setting of setting
group
γ
R
setSrcRef
ObjectReference
SP STUB BUS DISCONNECT setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
07
ORG
STUB BUS TRIGGER setting of setting group
γ
R
setSrcRef
ObjectReference
SP STUB BUS TRIGGER setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
08
ORG
DD NON-CURRENT SUPV setting
R
setSrcRef
ObjectReference
SP DD NON-CURRENT SUPV setting Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
09
ORG
DD CONTROL LOGIC setting of setting group
γ
R
setSrcRef
ObjectReference
SP DD CONTROL LOGIC setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
10
ORG
DD LOGIC SEAL-IN setting of setting group
γ
R
setSrcRef
ObjectReference
SP DD LOGIC SEAL-IN setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
12
ORG
Only instantiated in L90
R
setSrcRef
ObjectReference
SP 87L TRIP SUPV setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
13
ORG
Only instantiated in L90
R
setSrcRef
ObjectReference
SP 87L TRIP FORCE 3-
φ
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
LinDf0MMXU1
LDevice inst:
Prot
UR element:
Line Differential element (ANSI 87L) – local terminal current
function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
A
WYE
Local terminal currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
LOCAL I
θ
magnitude, in primary
amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
LOCAL I
θ
an
UR range -180...+180 converted to 0...360
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
LOCAL I
θ
magnitude, in primary
amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
LOCAL I
θ
an
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
LNName:
LinDfPDIF1
LDevice inst:
Prot
UR element:
Line Differential element (ANSI 87L) phase and general
functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...