RP470A and B 

Pneumatic Selector Relays 

INSTALLATION INSTRUCTIONS 

DESCRIPTION 

RP470A and B are three-port relays with the following 

differences: 

RP470A: 

  

Transmits the higher of two input signals. 

  

Selects the higher pressure with a sensitivity of .015 

psi (1.03 kPa). 

  

Is used in sensor lines, such as LP914 or LP915 

temperature sensors with a 1.25 to 2.50°F (0.68 to 
1.3°C) accuracy, depending on sensor span. 

  

Has a gray body. 

RP470B: 

  

Locks out one pressure signal when a second 
pressure signal is higher. 

  

Functions as a repeater for signal isolation. 

  

Functions as a lower-of-two-pressures selector. 

  

Has a gray and black body. 

Fig. 1 shows RP4

7

0A and B dimensions in inches 

(millimeters.) 

3

1-1/2 

(38)  

(25) 

C3211 

Fig. 1. RP470A and B dimensions. 

BEFORE INSTALLATION 

In a lower-of-two-pressures application, the RP470B 

requires a 0.007 Filter Restrictor 14002913-002 if the 
input is not already restricted (a one-pipe device input.) 

INSTALLATION 

Mounting 

Suspend on tubing or mount on a surface. See Fig. 2. for 

surface mounting. 

WALL OR 

PANEL 

RELAY 

NO. 10 X 1/2 IN. 
SHEET METAL SCREW 
(OBTAIN LOCALLY) 

MOUNTING CLIP 
(PROVIDED) 

C3214-1 

Fig. 2. Typical surface mounting. 

Piping 

Fig. 3 shows adaptation piping. All connections are sharp 

barb 5/32 in. (4 mm) O.D. polyethylene tubing. 

CAUTION 

To prevent damage to the sharp barb 
connections, do not attempt to cut or pull the 
tubing. To remove tubing from barb 
connections, cut tubing a few inches from the 
control device. Use a coupling to reconnect 
tubing. 

® U.S. Registered Trademark 
Copyright © 2002 Honeywell •   All Rights Reserved 

95-7231EF 

Summary of Contents for RP470A

Page 1: ... 2 1 1 2 38 25 C3211 Fig 1 RP470A and B dimensions 3 5 2 1 BEFORE INSTALLATION In a lower of two pressures application the RP470B requires a 0 007 Filter Restrictor 14002913 002 if the input is not already restricted a one pipe device input INSTALLATION Mounting Suspend on tubing or mount on a surface See Fig 2 for surface mounting WALL OR PANEL RELAY NO 10 X 1 2 IN SHEET METAL SCREW OBTAIN LOCALL...

Page 2: ...re that the higher of two input pressures at Ports 3 and 5 is transmitted through output Port 2 RP470B Lockout Relay or Repeater In a lockout relay application ensure that the relay passes the signal at Port 2 to Port 3 if the pressure at Port 5 is lower than the pressure at Port 2 When the pressure at Port 5 is greater than the pressure at Port 2 lockout should occur In a lower of two pressures a...

Page 3: ...those having 0 007 restrictors 0 15 psi 1 03 kPa Fig 6 shows a typical application using three zone thermostats and two RP470A for control Each zone is controlled by a separate thermostat The thermostat that calls for the most cooling transmits the highest branchline pressure controls the cooling valve through one or both RP470A ZONE 1 DA THERMOSTAT ZONE 2 DA THERMOSTAT ZONE 3 DA THERMOSTAT N C DA...

Page 4: ...ssures selection Fig 10 shows the RP470B piped for the lowest of two pressures selection with a capacity type device input INPUT 1 RP470B RESTRICTOR EXH CAPACITY TYPE DEVICE INPUT 2 5 3 OUTPUT C4488 Fig 10 RP470B piped for lowest of two pressures selection with capacity type device input Fig 11 shows the RP470B piped for a lowest of two pressures selection with a one pipe bleed type device input I...

Page 5: ...s Corps gris et noir La Fig 1 donne l encombrement en millimètres pouces des RP470A et B 3 2 38 1 1 2 1 CF3211 Fig 1 Encombrement des RP470A et B 3 5 2 25 AVANT D INSTALLER CE PRODUIT Dans une application de commande par la plus basse de deux pressions il faut ajouter au RP470B un réducteur filtre de 0 018 mm pièce 14002913 002 si l entrée n est pas déjà réduite entrée d un appareil à un tuyau INS...

Page 6: ...isé comme dispositif de blocage RP470B RP405A RP407 RP904A RO48B Sortie 3 P1 M P1 1 2 Pilote 5 P2 P P2 4 5 Entrée 2 B B1 B 3 Canal princ M VÉRIFICATION ET ESSAI RP470A Relais de commande par la plus élevée de deux pressions S assurer que la plus élevée de deux pressions aux orifices 3 et 5 est acheminée dans l orifice de sortie 2 RP470B Relais de blocage ou répéteur Dans une application avec relai...

Page 7: ...Elle est de 2 07 kPa 0 30 psi comparativement à 1 03 kPa 0 15 psi dans les circuits comportant des réducteurs de 0 018 mm La Fig 6 montre une application type avec des thermostats à trois zones et deux relais de commande RP470A Chaque zone est commandée par un thermostat distinct Le thermostat exigeant le plus de refroidissement qui transmet la pression la plus élevée dans la canalisation secondai...

Page 8: ...essions avec une entrée munie d un capteur à variation de puissance ENTRÉE 1 2 5 3 RP470B RÉDUCTEUR PURGE ENTRÉE AVEC CAPTEUR À VARIATION DE PUISSANCE SORTIE CF4488 Fig 10 RP470B installé comme relais sélecteur de la plus basse de deux pressions avec une entrée munie d un capteur à variation de puissance La Fig 11 montre un RP470B installé comme relais sélecteur de la plus basse de deux pressions ...

Reviews: