CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-97
2
"
713C
Ground Distance Zone 1 Z0 Z1 Angle
-90 to 90
degrees 1
F002
0
"
713D
Ground Distance Zone 1 RCA
30 to 90
degrees 1
F001
85
"
713E
Ground Distance Zone 1 DIR RCA
30 to 90
degrees 1
F001
85
"
713F
Ground Distance Zone 1 DIR Comp Limit
30 to 90
degrees 1
F001
90
"
7140
Ground Distance Zone 1 Quad Right Blinder 0.02 to 500
ohms
0.01
F001
1000
"
7141
Ground Distance Zone 1 Quad Right Blinder
RCA
60 to 90
degrees 1
F001
85
"
7142
Ground Distance Zone 1 Quad Left Blinder 0.02 to 500
ohms
0.01
F001
1000
"
7143
Ground Distance Zone 1 Quad Left Blinder
RCA
60 to 90
degrees 1
F001
85
"
7144
Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7
---
0.01
F001
0
"
7145
Ground Distance Zone 1 Z0M Z1 Angle
-90 to 90
degrees 1
F002
0
"
7146
Ground Distance Zone 1 Voltage Level
0 to 5
pu
0.001 F001
0
"
7147
Ground Distance Zone 1 Non-
Homogeneous Angle
-40 to 40
degrees 0.1
F002
0
"
7148
Ground Distance Zone 1 POL Current
0 to 1
---
1
F521
0 (Zero-seq)
"
7149
Ground Distance Zone 1 Reverse Reach
0.02 to 500
ohms
0.01
F001
200
"
714A
Ground Distance Zone 1 Reverse Reach
RCA
30 to 90
degrees 1
F001
85
"
714B
Reserved (7 items)
0 to 65535
---
1
F001
0
"
7152
...Repeated for Ground Distance Zone 2
"
7174
...Repeated for Ground Distance Zone 3
D30, D60, L90,
T60
7196
...Repeated for Ground Distance Zone 4
"
71B8
...Repeated for Ground Distance Zone 5
Line Pickup (Read/Write Grouped Setting)
D30, D60, L60,
L90
71E0
Line Pickup Function
0 to 1
---
1
F102
0 (Disabled)
"
71E1
Line Pickup Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
71E2
Line Pickup Phase IOC Pickup
0 to 30
pu
0.001 F001
1000
"
71E3
Line Pickup UV Pickup
0 to 3
pu
0.001 F001
700
"
71E4
Line End Open Pickup Delay
0 to 65.535
s
0.001 F001
150
"
71E5
Line End Open Reset Delay
0 to 65.535
s
0.001 F001
90
"
71E6
Line Pickup OV Pickup Delay
0 to 65.535
s
0.001 F001
40
"
71E7
Autoreclose Coordination Pickup Delay
0 to 65.535
s
0.001 F001
45
"
71E8
Autoreclose Coordination Reset Delay
0 to 65.535
s
0.001 F001
5
"
71E9
Autoreclose Coordination Bypass
0 to 1
---
1
F102
1 (Enabled)
"
71EA
Line Pickup Block
0 to 4294967295
---
1
F300
0
"
71EC
Line Pickup Target
0 to 2
---
1
F109
0 (Self-reset)
"
71ED
Line Pickup Events
0 to 1
---
1
F102
0 (Disabled)
"
71EE
Terminal Open
0 to 4294967295
---
1
F300
0
"
71F0
Autoreclose Accelerate
0 to 4294967295
---
1
F300
0
"
71F2
Distance Trip
0 to 1
---
1
F102
1 (Enabled)
Phase Directional Overcurrent (Read/Write Grouped Setting) (1 or 2 Modules)
C70, D30, D60,
F60, G30, G60,
L30, L60, L90,
M60, T60
7200
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7201
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
7202
Phase Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...