3-122
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6 General (Gen) logical device
The Ctrl logical device contains logical nodes that model UR FlexLogic, Virtual Outputs, non-volatile latches, FlexElements,
and recording (for example, oscillography) functions.
The Ctrl logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
3.5.6.1 Logical node zero (LLN0)
LLN0 is instantiated in all UR series devices implementing the Gen logical device.
Table 3-109: LLN0 data objects
3.5.6.2 Data logger (DatLog)
This element is instantiated in the following products: C30, C60, C70, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35,
T60.
Table 3-110: Data logger data objects
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF EnrMtrMMTR1.RsStat.ctlModel
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
R/W/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
InRef1
ORG
CLEAR ENERGY setting.
R
setSrcRef
ObjectReference
SP setting reference to clear Energy,
which shows the receiving of
dynamically clearing signal for
energy calculation
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName: LLN0
LDevice inst: Gen
data obj. data attribute
Type
FC UR Name
Description
R/W/C
NamPlt
LPL
Logical node Prot configuration
information
R
vendor
VISIBLE
STRING255
DC
Mapped to LPHD1/PhyNam.vendor
R
swRev
VISIBLE
STRING255
DC
Mapped to LPHD1/PhyNam.swRev
R
configRev
VISIBLE
STRING255
DC Gen configRev
The factory default value is the empty
string
R
ldNs
VISIBLE
STRING255
EX
IEC 61850-7-4:2007B
R
GrRef
ORG
Reference to the next higher-level
logical device (LD)
R
setSrcRef
ObjectReference SP
In communications, the Master ldName
setting if not empty, otherwise the
concatenation of the IED name and
“Master”.
In SCL, the concatenation of the IED
name and “Master”.
R
LNName:
DatLogRDRE1
LDevice inst:
Gen
UR element:
Data Logger
data obj. data attribute
Type
FC UR Name
Description
R/W/C
FltNum
INS
Fault number
R
LNName:
EnrMtrMMTR#
LDevice inst:
Meter
UR element:
Signal Source # Energy Metering
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...