CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-95
2
"
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees 1
F001
90
"
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001 F001
0
"
7076
Phase Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
"
7078
Phase Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7079
Phase Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
707A
Phase Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
Fixed in G60
"
707B
Phase Distance Zone 1 RCA
30 to 90
degrees 1
F001
85
"
707C
Phase Distance Zone 1 DIR RCA
30 to 90
degrees 1
F001
85
"
707D
Phase Distance Zone 1 DIR Comp Limit
30 to 90
degrees 1
F001
90
"
707E
Phase Distance Zone 1 Quad Right Blinder 0.02 to 500
ohms
0.01
F001
1000
"
707F
Phase Distance Zone 1 Quad Right Blinder
RCA
60 to 90
degrees 1
F001
85
"
7080
Phase Distance Zone 1 Quad Left Blinder
0.02 to 500
ohms
0.01
F001
1000
"
7081
Phase Distance Zone 1 Quad Left Blinder
RCA
60 to 90
degrees 1
F001
85
"
7082
Phase Distance Zone 1 Volt Limit
0 to 5
pu
0.001 F001
0
"
7083
Phase Distance Zone 1 Transformer
Voltage Connection
0 to 12
---
1
F153
0 (None)
"
7084
Phase Distance Zone 1 Transformer
Current Connection
0 to 12
---
1
F153
0 (None)
"
7085
Phase Distance Zone 1 Rev Reach
0.02 to 500
ohms
0.01
F001
200
"
7086
Phase Distance Zone 1 Rev Reach RCA
30 to 90
degrees 1
F001
85
"
7087
Reserved (10 items)
---
---
---
F001
0
"
7091
...Repeated for Phase Distance Zone 2
"
70B2
...Repeated for Phase Distance Zone 3
D30, D60, L90
T60
70D3
...Repeated for Phase Distance Zone 4
"
70F4
...Repeated for Phase Distance Zone 5
Breaker Failure (Read/Write Grouped Setting) (24 Modules)
B90
7100
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7101
Breaker Failure 1 Initiate
0 to 4294967295
---
1
F300
0
"
7103
Breaker Failure 1 Use Amp Supervision
0 to 1
---
1
F126
1 (Yes)
"
7104
Breaker Failure 1 Use Seal In
0 to 1
---
1
F126
1 (Yes)
"
7105
Breaker Failure 1 Amp Supervision OpA
0 to 4294967295
---
1
F300
0
"
7107
Breaker Failure 1 Amp Supervision OpB
0 to 4294967295
---
1
F300
0
"
7109
Breaker Failure 1 Amp Supervision OpC
0 to 4294967295
---
1
F300
0
"
710B
Breaker Failure 1 Use Timer1
0 to 1
---
1
F126
1 (Yes)
"
710C
Breaker Failure 1 Timer1 Pickup Delay
0 to 65.535
s
0.001 F001
0
"
710D
Breaker Failure 1 Use Timer2
0 to 1
---
1
F126
1 (Yes)
"
710E
Breaker Failure 1 Timer2 Pickup Delay
0 to 65.535
s
0.001 F001
0
"
710F
Breaker Failure 1 Use Timer3
0 to 1
---
1
F126
1 (Yes)
"
7110
Breaker Failure 1 Timer3 Pickup Delay
0 to 65.535
s
0.001 F001
0
"
7111
Breaker Failure 1 Breaker Pos1
0 to 4294967295
---
1
F300
0
"
7113
Breaker Failure 1 Breaker Pos2
0 to 4294967295
---
1
F300
0
"
7115
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
"
7117
Breaker Failure 1 Amp Hiset OpA
0 to 4294967295
---
1
F300
0
"
7119
Breaker Failure 1 Amp Hiset OpB
0 to 4294967295
---
1
F300
0
"
711B
Breaker Failure 1 Amp Hiset OpC
0 to 4294967295
---
1
F300
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...