3.5.1.3 Physical device information (LPHD1)
LPHD1 is instantiated in all UR series devices.
Table 3-12: Physical device data objects
LNName:
LPHD1
LDevice inst:
Master
UR element:
data obj. data attribute
Type
FC UR Name
Description
R/W/C
PhyNam
DPL
This physical device’s name plate
R
vendor
VISIBLE
STRING255
DC “GE Multilin”
R
swRev
VISIBLE
STRING255
DC Firmware revision, for example
“7.30”
R
serNum
VISIBLE
STRING255
DC The serial number of this unit
R
model
VISIBLE
STRING255
DC The order code of this unit
R
location
VISIBLE
STRING255
DC Location
R/C
name
VISIBLE STRING64 DC RELAY NAME
On import, any characters after the 20th
are truncated
R/C
latitude
FLOAT32
DC Latitude
R/C
longitude
FLOAT32
DC Longitude
R/C
altitude
FLOAT32
DC Altitude
R/C
PhyHealth
ENS
This physical device’s health
R
stVal
ENUMERATED
ST
3 when ANY MAJOR ERROR==On; 2 when
ANY MINOR ERROR==On, otherwise 1
R
Proxy
SPS
Indicates if this LN is a proxy
R
stVal
BOOLEAN
ST
R
RsStat
SPC
Mapped to command CLEAR ALL RELAY
RECORDS
R/Ctrl
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32
0 indicates the duration is locally defined
R
pulseConfig
.offDur
INT32
0
R
pulseConfig
.numPls
INT32
1
R
ctlModel
CtlModels
CF LPHD1.RsStat.ctlModel
1, the code for direct control with normal
security; 2 is code for SBO with normal
security; 0 is for status only according to IEC
61850-7-2. Enhanced security is not
supported as there is no means of
confirming successful execution of the
control command.
R/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
Sim
SPC
Will accept simulated GOOSE messages
R
stVal
BOOLEAN
ST
R
ctlModel
CtlModels
CF
0
R/C
AnyErr
SPS
ANY SELF TESTS operand
R
stVal
BOOLEAN
ST ANY SELF TESTS
R
MajorErr
SPS
ANY MAJOR ERROR operand
R
stVal
BOOLEAN
ST ANY MAJOR ERROR
R
MinorErr
SPS
ANY MINOR ERROR operand
R
stVal
BOOLEAN
ST ANY MINOR ERROR
R
BatFail
SPS
BATTERY FAIL operand
R
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...