2-98
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
7204
Phase Directional Overcurrent 1 ECA
0 to 359
---
1
F001
30
"
7205
Phase Directional Overcurrent 1 Pol V
Threshold
0 to 3
pu
0.001 F001
700
"
7206
Phase Directional Overcurrent 1 Block
Overcurrent
0 to 1
---
1
F126
0 (No)
"
7207
Phase Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7208
Phase Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
7209
Reserved (8 items)
0 to 1
---
1
F001
0
C70, D30, D60,
F60, L30, L60,
L90, M60
7211
...Repeated for Phase Directional
Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (1 or 2 Modules)
C70, D30, D60,
F60, G30, G60,
L30, L60, L90,
M60, T60
7230
Neutral Directional Overcurrent 1 Function 0 to 1
---
1
F102
0 (Disabled)
"
7231
Neutral Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
7232
Neutral Directional Overcurrent 1 Polarizing 0 to 4
---
1
F230
0 (Voltage)
"
7233
Neutral Directional Overcurrent 1 Forward
ECA
-90 to 90
° Lag
1
F002
75
"
7234
Neutral Directional Overcurrent 1 Forward
Limit Angle
40 to 90
degrees 1
F001
90
"
7235
Neutral Directional Overcurrent 1 Forward
Pickup
0.006 to 30
pu
0.001 F001
50
"
7236
Neutral Directional Overcurrent 1 Reverse
Limit Angle
40 to 90
degrees 1
F001
90
"
7237
Neutral Directional Overcurrent 1 Reverse
Pickup
0.006 to 30
pu
0.001 F001
50
"
7238
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7239
Neutral Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
"
723B
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
723C
Neutral Directional Overcurrent 1 Polarizing
Voltage
0 to 1
---
1
F231
0
(Calculated
V0)
"
723D
Neutral Directional Overcurrent 1 Op
Current
0 to 1
---
1
F196
0
(Calculated
3I0)
"
723E
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
"
723F
Neutral Directional Overcurrent 1 Pos Seq
Restraint
0 to 0.5
---
0.001 F001
63
"
7240
Reserved
0 to 1
---
1
F001
0
D30, D60, F60,
G30, G60, L30,
L60, L90, M60
7241
...Repeated for Neutral Directional
Overcurrent 2
Negative-Sequence Directional Overcurrent (Read/Write Grouped Settings) (2 Modules)
C70, D30, D60,
F60, G30, G60,
L60, L90
7260
Negative Sequence Directional Overcurrent
1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7261
Negative Sequence Directional Overcurrent
1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
7262
Negative Sequence Directional Overcurrent
1 Type
0 to 1
---
1
F179
0 (Neg
Sequence)
"
7263
Neg Sequence Directional Overcurrent 1
Forward ECA
0 to 90
° Lag
1
F002
75
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...