CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-29
2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2, 4, or 6 Modules)
C60, D60, F35,
L90, T35, T60
21FA
...Repeated for Breaker 3
"
21FE
...Repeated for Breaker 4
F35, T35
2208
...Repeated for Breaker 5
"
2212
...Repeated for Breaker 6
Bus Actuals (Read Only) (6 Modules)
B90
2208
...Repeated for Bus Zone 5
"
2212
...Repeated for Bus Zone 6
Breaker Arcing Current Commands (Read/Write Command) (2, 4, or 6 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90, T35,
T60
2224
Breaker 1 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
"
2225
Breaker 2 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
C60, D60, F35,
L90, T35, T60
2226
Breaker 3 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
"
2227
Breaker 4 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
F35, T35
2228
Breaker 5 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
"
2229
Breaker 6 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
Passwords Unauthorized Access (Read/Write Command)
All
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Hi-Z (High Impedance Fault Detection) Commands (Read/Write Command)
F60
2240
Hi-Z Clear Oscillography
0 to 1
---
1
F126
0 (No)
"
2241
Hi-Z Oscillography Force Trigger
0 to 1
---
1
F126
0 (No)
"
2242
Hi-Z Oscillography Force Algorithm Capture 0 to 1
---
1
F126
0 (No)
"
2243
Hi-Z Reset Sigma Values
0 to 1
---
1
F126
0 (No)
Hi-Z (High Impedance Fault Detection) Status (Read Only)
F60
2250
Hi-Z Status
0 to 9
---
1
F187
0 (NORMAL)
"
2251
Hi-Z Phase A Arc Confidence
0 to 100
---
1
F001
0
"
2252
Hi-Z Phase B Arc Confidence
0 to 100
---
1
F001
0
"
2253
Hi-Z Phase C Arc Confidence
0 to 100
---
1
F001
0
"
2254
Hi-Z Neutral Arc Confidence
0 to 100
---
1
F001
0
Hi-Z (High Impedance Fault Detection) Records (Read Only) (4 Modules)
F60
2260
Hi-Z Capture 1 Trigger Type
0 to 6
---
1
F188
0 (NONE)
"
2261
Hi-Z Capture 1 Time
0 to 1
---
1
F050
0
"
2263
...Repeated for Hi-Z Capture 2
"
2266
...Repeated for Hi-Z Capture 3
"
2269
...Repeated for Hi-Z Capture 4
Hi-Z (High Impedance Fault Detection) RMS Records (Read Only) (4 Modules)
F60
2270
Hi-Z RMS Capture 1 Trigger Type
0 to 6
---
1
F188
0 (NONE)
"
2271
Hi-Z RMS Capture 1 Time
0 to 1
---
1
F050
0
"
2273
...Repeated for Hi-Z RMS Capture 2
"
2276
...Repeated for Hi-Z RMS Capture 3
"
2279
...Repeated for Hi-Z RMS Capture 4
Source Current THD (Read Only) (6 Modules)
L60
22A0
Source 1 Ia THD
0 to 100
%
0.1
F001
0
"
22A1
Source 1 Ib THD
0 to 100
%
0.1
F001
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...