CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-45
3
3.5.2.12 Compensated overvoltage (CompOv)
This element is instantiated in the following products: D60.
Table 3-30: D60 compensated overvoltage function data objects
Table 3-31: D60 compensated overvoltage stage data objects
phs
θ
.cVal.mag.f
FLOAT32
BUS # REST I
θ
r magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
BUS # REST
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF BusDifPDIF#.DifAClc.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
InRef2
τ
ORG
BUS ZONE #
τ
STATUS setting
R
setSrcRef
ObjectReference
SP BUS ZONE #
τ
STATUS setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef
γ
ORG
BUS ZONE # DIFF BLK setting for setting
group
γ
R
setSrcRef
ObjectReference
SP BUS ZONE # DIFF BLK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
CmpOv0PTOV1
LDevice inst:
Prot
UR element:
Compensated Overvoltage functions.
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
COMP OV PKP operand
R
general
BOOLEAN
ST COMP OV PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
COMP OV OP operand
R
general
BOOLEAN
ST COMP OV OP
R
Dpo
SPS
COMP OV DPO operand, which is the inverse
of COMP OV PKP
R
stVal
BOOLEAN
ST COMP OV DPO
R
BlkRef
γ
ORG
COMPENSATED OV BLK setting for setting
group
γ
R
setSrcRef
ObjectReference
SP COMPENSATED OV BLK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
CmpOvPTOV$
LDevice inst:
Prot
UR element:
Compensated Overvoltage stage $.
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
COMP OV STG$ PKP operand
R
general
BOOLEAN
ST COMP OV STG$ PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
COMP OV STG$ OP operand
R
general
BOOLEAN
ST COMP OV STG$ OP
R
Dpo
SPS
COMP OV STG$ DPO operand, which is the
inverse of COMP OV STG$ PKP
R
stVal
BOOLEAN
ST COMP OV STG$ DPO
R
LNName:
BusDifPDIF#
LDevice inst:
Prot
UR element:
Bus Differential element # (ANSI 87B)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...