CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-105
3
VaRMS
MV
SRC # Phase AG Voltage RMS, in primary
volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
SRC # Phase AG Voltage RMS
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for primary volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF MMXU# RMS PhV.phsA
DEADBAND
R/W/C
zeroDb
INT32U
CF
Voltage cut-off level
R
VbRMS
MV
SRC # Phase BG Voltage RMS, in primary
volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
SRC # Phase BG Voltage RMS
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for primary volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF MMXU# RMS PhV.phsB
DEADBAND
R/W/C
zeroDb
INT32U
CF
Voltage cut-off level
R
VcRMS
MV
SRC # Phase CG Voltage RMS, in primary
volts
R
instMag
AnalogueValue MX
R
instMag.f
FLOAT32
SRC # Phase CG Voltage RMS
R
mag
AnalogueValue MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for primary volts (W/A)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF MMXU# RMS PhV.phsC
DEADBAND
R/W/C
zeroDb
INT32U
CF
Voltage cut-off level
R
LNName: ACsrcMMXU#
LDevice inst: Meter
UR element: AC Source #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...