CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-107
2
"
7C80
...Repeated for User Programmable
Pushbutton 7
"
7CB0
...Repeated for User Programmable
Pushbutton 8
"
7DE0
...Repeated for User Programmable
Pushbutton 9
"
7D10
...Repeated for User Programmable
Pushbutton 10
"
7D40
...Repeated for User Programmable
Pushbutton 11
"
7D70
...Repeated for User Programmable
Pushbutton 12
"
7DA0
...Repeated for User Programmable
Pushbutton 13
"
7DD0
...Repeated for User Programmable
Pushbutton 14
"
7E00
...Repeated for User Programmable
Pushbutton 15
"
7E30
...Repeated for User Programmable
Pushbutton 16
High Impedance Fault Detection (Hi-Z) Settings (Read/Write Setting)
F60
7E60
Hi-Z Function
0 to 1
---
1
F102
0 (Disabled)
"
7E61
Hi-Z Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
7E62
Hi-Z Arcing Sensitivity
1 to 10
---
1
F001
5
"
7E63
Hi-Z Phase Event Count
10 to250
---
1
F001
30
"
7E64
Hi-Z Ground Event Count
10 to 500
---
1
F001
30
"
7E65
Hi-Z Event Count Time
5 to 180
min
1
F001
15
"
7E66
Hi-Z OC Protection Coord Timeout
10 to 200
seconds 1
F001
15
"
7E67
Hi-Z Phase OC Min Pickup
0.01 to 10
pu
0.01
F001
150
"
7E68
Hi-Z Neutral OC Min Pickup
0.01 to 10
pu
0.01
F001
100
"
7E69
Hi-Z Phase Rate of Change
1 to 999
A/2cycle 1
F001
150
"
7E6A
Hi-Z Neutral Rate of Change
1 to 999
A/2cycle 1
F001
150
"
7E6B
Hi-Z Loss of Load Threshold
5 to 100
%
1
F001
15
"
7E6C
Hi-Z Three-Phase Event Threshold
1 to 1000
A
1
F001
25
"
7E6D
Hi-Z Voltage Supv Threshold
0 to 100
%
1
F001
5
"
7E6E
Hi-Z Voltage Supv Delay
0 to 3000
cycles
2
F001
60
"
7E6F
Hi-Z Even Harmonic Restraint
0 to 100
%
1
F001
20
"
7E70
Hi-Z Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E71
Hi-Z Events
0 to 1
---
1
F102
0 (Disabled)
"
7E72
Hi-Z Arcing Reset Time
0 to 6000
seconds 0.1
F001
0
Field Current (Read/Write Grouped Setting)
G60
7E74
Field Current Function
0 to 1
---
1
F102
0 (Disabled)
"
7E75
Field Current Origin
0 to 48
---
1
F151
0 (NONE)
"
7E76
Field Current OC Pickup
0.05 to 1
pu
0.01
F001
80
"
7E77
Field Current OC Delay
0 to 600
seconds 0.01
F001
100
"
7E78
Field Current UC Pickup
0.05 to 1
pu
0.01
F001
20
"
7E79
Field Current UC Delay
0 to 600
seconds 0.01
F001
100
"
7E7A
Field Current Block
0 to 4294967295
---
1
F300
0
"
7E7C
Field Current Target
0 to 2
---
1
F109
0 (Self-reset)
"
7E7D
Field Current Events
0 to 1
---
1
F102
0 (Disabled)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...