background image

PCM-07/U TIME RELAY

 

INSTRUCTION MANUAL

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamelcet.com

, e-mail: [email protected]

APPEARANCE

FEATURES

TECHNICAL DATA

DESCRIPTION

PCM-07/U

Power supply terminals: A1, A2

Input rated voltage: 24÷250 V AC, 30÷300 V DC

Nominal frequency:  50 / 60 Hz

Rated power consumption: 2 W / 14 VA

Operating mode release terminals:

S, S

Permanent switch on/switch off terminals:

IN, IN

Number of operating modes: 25

Operating modes: manual, automatic

Time adjustment range t: 0,1 sec ÷ 99 h 59 min 59,9 sec

Time adjustment accuracy: 0,1 s

LCD display backlight:

amber

Time measure accuracy: max. ±3 s / 24 h with 25 °C

Hold up programme time: 10 years

Receiver input (supply) terminals: 11, 12, 14, 21, 22, 24

Output relay parameters: 2 NO/NC 16 A 250 V AC1 4000 VA

Number of terminal clamps:  12

Section of connecting cables:  0,2 ÷ 2,50 mm

2

Ambient temperature range: -20 ÷ +60 

o

C

Operating position: freely

Mounting: rail TH 35 (PN-EN 60715)

Protection degree: IP20 (PN-EN 60529)

Protection level: 

II

Overvoltage category:

II

Pollution degree: 2

Dimensions: double-modular (35 mm) 90x35x66 mm

Weight: 0,130 kg

Reference standards: PN-EN 60730-1; PN-EN 60730-2-7

 

PN-EN 61000-4-2,3,4,5,6,11

● 25 operating modes (external release 

or from power supply voltage),

● double-modular casing with a security 

cover,

● S input (start) and an additional IN 

control input (permanent switch on / 

switch off),

● time measure accuracy,

● wide time adjustment range,

● permanent switch on or switch off 

function,

● voltage relay output – two change over 

contacts of max 16 A capacity,

● LCD display backlight,

● double-modular casing,

● TH-35 DIN rail installation.

The  multifunctional  digital  time  relay 

PCM-07/U has a time function in automa

-

tion  and  control  systems.  It  is  equipped 

with  25  independent  operating  modes 

released  by  power  supply  voltage  or  an 

external impulse command on S terminal 

(coming from L or N line). It has a really 

wide time adjustment range from 0,1 sec. 

to 99 h 59 min. 59,9 sec. And it has per

-

manent switch on / switch off functions by 

means  of  IN  input. The  mode  change  is 

possible without waiting for the current cy

-

cle to be finished.

The  device  is  designed  for 

single-phase installation and 

must  be  installed  in  accor

-

dance  with  standards  valid 

in  a  particular  country.  The 

device should be connected 

according to the details inc

-

luded in this operating manual. Installation, 

connection  and  control  should  be  carried 

out by a qualified electrician staff, who act 

in accordance with the service manual and 

the device functions. Disassembling of the 

device  is  equal  with  a  loss  of  guarantee 

and  can  cause  electric  shock.  Before  in

-

stallation make sure the connection cables 

are not under voltage. The cruciform head 

screwdriver 3,5 mm should be used to in

-

stal the device. Improper transport, storage, 

and  use  of  the  device  influence  its  wrong 

functioning. 

It is not advisable to instal the device in the 

following cases: if any device part is missing 

or the device is damaged or deformed. In 

case of improper functioning of the device 

contact the producer.

CAUTION

Manual mode

Automatic mode

Relay mode

Information field

Operating mode 
number or time

adjustment number

Power supply terminals
(A1, A2)

LCD display

Operating mode release 

terminals (S, S)

Permanent

 

switch on/switch off

terminals (IN, IN)

Control push buttons

Relays output (supply) terminals
(12, 11, 14, 24, 21, 22)

VER. 002_01.09.2009

The symbol means selective  

collecting of electrical and electronical 

equipment. It is forbidden to put  

the used equipment together  

with other waste

Summary of Contents for PCM-07/U

Page 1: ... The multifunctional digital time relay PCM 07 U has a time function in automa tion and control systems It is equipped with 25 independent operating modes released by power supply voltage or an external impulse command on S terminal coming from L or N line It has a really wide time adjustment range from 0 1 sec to 99 h 59 min 59 9 sec And it has per manent switch on switch off functions by means o...

Page 2: ... to confirm To confirm all the adjustments press OK confirming the command allows to enter the time adjustment window The system is equipped with protection against 0h0m0s0ss 0 1 sec is the minimum time time adjustment in menu similarly to menu system mode adjustment suitable for the moment of releasing external input IN the system operates in this mode as long as there is a releasing signal on ex...

Page 3: ...ggerable SWITCH ON OFF DELAY non retriggerable after the impulse release has been applied to the power supply system rising edge it lets the relay be switched off pos 11 12 at the same time starts the preset time t1 measurement After the time is over the relay is swit ched on pos 11 14 After the impulse release fade is detected falling modulated voltage the system starts preset time t2 measuremnt ...

Page 4: ...unction box Ø60 version Device symbol The main switch L N The acoustic signal system of starting the machine engine Operating adjusted to WARRANTY CARD There is 24 months guarantee on the product Salesman stamp and signature date of sale 1 ZMIE ZAMEL SP J assures 24 months guarantee for the product 2 The manufacturer s guarantee does not cover any of the following actions a mechanical damage durin...