CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-139
2
"
B244
...Repeated for Received Analog 27
"
B246
...Repeated for Received Analog 28
"
B248
...Repeated for Received Analog 29
"
B24A
...Repeated for Received Analog 30
"
B24C
...Repeated for Received Analog 31
"
B24E
...Repeated for Received Analog 32
Wattmetric Ground Fault Settings (Read/Write Grouped) (2 or 4 Modules)
D60, F35, F60,
L60, L90
B300
Wattmetric Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
B301
Wattmetric Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
B302
Wattmetric Ground Fault 1 Voltage
0 to 1
---
1
F234
0
(Calculated
VN)
"
B303
Wattmetric Ground Fault 1 Overvoltage
Pickup
0.02 to 3.00
pu
0.01
F001
20
"
B304
Wattmetric Ground Fault 1 Current
0 to 1
---
1
F235
0
(Calculated
IN)
"
B305
Wattmetric Ground Fault 1 Overcurrent
Pickup
0.002 to 30.000
pu
0.001 F001
60
"
B306
Wattmetric Ground Fault 1 Overcurrent
Pickup Delay
0 to 600
s
0.01
F001
20
"
B307
Wattmetric Ground Fault 1 Power Pickup
0.001 to 1.2
pu
0.001 F001
100
"
B308
Wattmetric Ground Fault 1 ECA
0 to 360
° Lag
1
F001
0
"
B309
Wattmetric Ground Fault 1 Power Pickup
Delay
0 to 600
s
0.01
F001
20
"
B30A
Wattmetric Ground Fault 1 Curve
0 to 5
---
1
F236
0 (Definite
Time)
"
B30B
Wattmetric Ground Fault 1 Multiplier
0.01 to 2
s
0.01
F001
100
"
B30C
Wattmetric Ground Fault 1 Block
0 to 4294967295
---
1
F300
0
"
B30E
Wattmetric Ground Fault 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
B30F
Wattmetric Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
B310
Wattmetric Ground Fault 1 Reference
Power
0.001 to 1.2
pu
0.001 F001
500
"
B311
Wattmetric Ground Fault 1 Reserved
0 to 1
---
1
F001
0
"
B312
...Repeated for Wattmetric Ground Fault 2
F35
B324
...Repeated for Wattmetric Ground Fault 3
"
B336
...Repeated for Wattmetric Ground Fault 4
Wattmetric Ground Fault Actual Values (Read Only) (2 or 4 Modules)
D60, F35, F60,
L60, L90
B360
Wattmetric Ground Fault 1 Operating
Power
0 to 999999.999
W
0.001 F060
0
"
B362
...Repeated for Wattmetric Ground Fault 2
F35
B364
...Repeated for Wattmetric Ground Fault 3
"
B366
...Repeated for Wattmetric Ground Fault 4
IEC 61850 XSWI Configuration (Read/Write Setting) (24 Modules)
All except B90
B370
FlexLogic Operand for IEC 61850
XSWI.ST.Loc Status
0 to 4294967295
---
1
F300
0
"
B372
FlexLogic Operand for IEC 61850 XSWI
Open Interlock
0 to 4294967295
---
1
F300
1
"
B374
FlexLogic Operand for IEC 61850 XSW
Close Interlock
0 to 4294967295
---
1
F300
1
"
B376
...Repeated for Switch 2
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...