CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-75
2
Capacitor Bank Overvoltage Settings (Read/Write, Grouped Setting) (3 Modules)
C70
6330
Bank Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
6331
Bank Phase Overvoltage 1 Bus Source
0 to 5
---
1
F167
0 (SRC 1)
"
6332
Bank Phase Overvoltage 1 Neutral Source 0 to 5
---
1
F167
0 (SRC 1)
"
6333
Bank Phase Overvoltage 1 Bank Ground
0 to 2
---
1
F093
0 (Grounded)
"
6334
Bank Phase Overvoltage 1 Curve
0 to 3
---
1
F094
0 (FlexCurve
A)
"
6335
Bank Phase Overvoltage 1 Curve Time
Multiplier
1 to 10
---
0.01
F001
100
"
6336
Bank Phase Overvoltage 1 Stage 1A Pickup 0.8 to 2
pu
0.001 F001
1050
"
6337
Bank Phase Overvoltage 1 Stage 2A Pickup 0.8 to 2
pu
0.001 F001
1100
"
6338
Bank Phase Overvoltage 1 Stage 3A Pickup 0.8 to 2
pu
0.001 F001
1200
"
6339
Bank Phase Overvoltage 1 Stage 4A Pickup 0.8 to 2
pu
0.001 F001
1050
"
633A
Bank Phase Overvoltage 1 Stage 1B Pickup 0.8 to 2
pu
0.001 F001
1050
"
633B
Bank Phase Overvoltage 1 Stage 2B Pickup 0.8 to 2
pu
0.001 F001
1100
"
633C
Bank Phase Overvoltage 1 Stage 3B Pickup 0.8 to 2
pu
0.001 F001
1200
"
633D
Bank Phase Overvoltage 1 Stage 4B Pickup 0.8 to 2
pu
0.001 F001
1050
"
633E
Bank Phase Overvoltage 1 Stage 1C Pickup 0.8 to 2
pu
0.001 F001
1050
"
633F
Bank Phase Overvoltage 1 Stage 2C Pickup 0.8 to 2
pu
0.001 F001
1100
"
6340
Bank Phase Overvoltage 1 Stage 3C Pickup 0.8 to 2
pu
0.001 F001
1200
"
6341
Bank Phase Overvoltage 1 Stage 4C Pickup 0.8 to 2
pu
0.001 F001
1050
"
6342
Bank Phase Overvoltage 1 Stage 1 Pickup
Delay
0 to 600
s
0.01
F001
6000
"
6343
Bank Phase Overvoltage 1 Stage 2 Pickup
Delay
0 to 600
s
0.01
F001
1000
"
6344
Bank Phase Overvoltage 1 Stage 3 Pickup
Delay
0 to 600
s
0.01
F001
200
"
6345
Bank Phase Overvoltage 1 Dropout Delay
0 to 600
s
0.01
F001
25
"
6346
Bank Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
"
6348
Bank Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
6349
Bank Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
634A
...Repeated for Bank Phase Overvoltage 2
"
6364
...Repeated for Bank Phase Overvoltage 3
Capacitor Bank Overvoltage Actuals (Read Only) (3 Modules)
C70
6390
Bank Overvoltage 1 Phase A Operate
Voltage
0 to 65.535
pu
0.001 F001
0
"
6391
Bank Overvoltage 1 Phase B Operate
Voltage
0 to 65.535
pu
0.001 F001
0
"
6392
Bank Overvoltage 1 Phase C Operate
Voltage
0 to 65.535
pu
0.001 F001
0
"
6393
...Repeated for Bank Overvoltage 2
"
6396
...Repeated for Bank Overvoltage 3
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
C70, D30, D60,
F35, F60, L30,
L60, L90
63C0
Negative Sequence Instantaneous OC 1
Function
0 to 1
---
1
F102
0 (Disabled)
"
63C1
Negative Sequence Instantaneous OC 1
Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
63C2
Negative Sequence Instantaneous
Overcurrent 1 Pickup
0 to 30
pu
0.001 F001
1000
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...