CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-67
3
3.5.2.40 Phase time overcurrent (PhsToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, T35, T60.
Table 3-61: Phase time overcurrent data objects
Op
ACT
PHASE OV # OP operand (including
individual three phases)
R
general
BOOLEAN
ST PHASE OV # OP
R
phsA
BOOLEAN
ST PHASE OV # OP A
R
phsB
BOOLEAN
ST PHASE OV # OP B
R
phsC
BOOLEAN
ST PHASE OV # OP C
R
Dpo
SPS
PHASE OV # DPO operand, which is the
inverse of PHASE OV PKP
R
stVal
BOOLEAN
ST PHASE OV # DPO
R
DpoPhs
β
SPS
PHASE OV# DPO
β
operand” (where
β
refers
to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE OV# DPO
β
(where
β
refers
to Phase-A, B or C)
R
BlkRef
γ
ORG
PHASE OV # BLK setting for setting group
γ
R
setSrcRef
ObjectReference
SP PHASE OV # BLK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PhsTocPTOC#
LDevice inst:
Prot
UR element:
Phase Time Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE TOC# PKP operands (including
individual three phases), which indicates
that Op operates when delay expires
R
general
BOOLEAN
ST PHASE TOC# PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
phsA
BOOLEAN
ST PHASE TOC# PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown
R
phsB
BOOLEAN
ST PHASE TOC# PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown
R
phsC
BOOLEAN
ST PHASE TOC# PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
PHASE TOC# OP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE TOC# OP
R
phsA
BOOLEAN
ST PHASE TOC# OP A
R
phsB
BOOLEAN
ST PHASE TOC# OP B
R
phsC
BOOLEAN
ST PHASE TOC# OP C
R
Dpo
SPS
PHASE TOC# DPO operand
R
stVal
BOOLEAN
ST PHASE TOC# DPO
R
DpoPhs
β
SPS
PHASE TOC# DPO
β
operands” (where
β
refers to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE TOC# DPO
β
(where
β
refers to Phase-A, B or C)
R
BlkRef
γβ
ORG
PHASE TOC# BLOCK
β
setting for setting
group
γ
.” (where
β
refers to Phase-A, B or C)
R
setSrcRef
ObjectReference
SP PHASE TOC# BLOCK
β
for group
γ
(where
β
refers to Phase-A, B or C)
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PhsOvPTOV#
LDevice inst:
Prot
UR element:
Phase Overvoltage element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...