3-116
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.5.3 B90 AC channel metering (B_Mtr)
This element is instantiated in the following products: B90.
Table 3-104: B90 AC channel metering data objects
Table 3-105: B90 AC channel metering data objects
c2.cVal.ang.f
FLOAT32
instCVal.ang.i deadbanded
R
c2.units
Unit
CF
R
c2.units.SIUnit
ENUMERATED
29, the code for primary volts (W/A)
R
c2.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
c2.db
INT32U
CF MSQI# Seq2 V DEADBAND
R/W/C
c2.zeroDb
INT32U
CF
Voltage cut-off level
R
c3
CMV
R
c3.instCVal
Vector
MX
R
c3.instCVal.mag.f
FLOAT32
SRC # Zero Sequence Voltage
Magnitude
R
c3.instCVal.ang.f
FLOAT32
SRC # Zero Sequence Voltage
Angle
UR range -180...+180 converted to 0...360
R
c3.cVal
Vector
MX
R
c3.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
c3.cVal.ang.f
FLOAT32
instCVal.ang.i deadbanded
R
c3.units
Unit
CF
R
c3.units.SIUnit
ENUMERATED
29, the code for primary volts (W/A)
R
c3.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
c3.db
INT32U
CF MSQI# Seq0 V DEADBAND
R/W/C
c3.zeroDb
INT32U
CF
Voltage cut-off level
R
seqT
ENUMERATED
MX
0, the code for pos-neg-zero
R
phsRef
ENUMERATED
CF
0, the code for phase A
R
LNName:
B_AmpMMXN#
LDevice inst:
Meter
UR element:
B90 Metering for current input
φ
data obj. data attribute
Type
FC UR Name
Description
R/W/C
ChA
CMV
φ
current in primary amps
R
instCVal
Vector
MX
R
instCVal.mag.f
FLOAT32
φ
CURRENT magnitude
R
instCVal.ang.f
FLOAT32
φ
CURRENT a
UR range -180...+180 converted to 0...360
R
cVal
Vector
MX
R
cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
cVal.ang.f
FLOAT32
instCVal.ang.i deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF B_AmpMMXN
φ
.ChA.db
R/W/C
zeroDb
INT32U
CF
R
LNName:
B_VolMMXN#
LDevice inst:
Meter
UR element:
B90 Metering for voltage input
φ
data obj. data attribute
Type
FC UR Name
Description
R/W/C
ChV
CMV
φ
voltage in primary volts
R
instCVal
Vector
MX
R
instCVal.mag.f
FLOAT32
φ
VOLTAGE magnitude
R
LNName:
ACsrcMSQI#
LDevice inst:
Meter
UR element:
AC Source #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...