![background image](http://html1.mh-extra.com/html/ge/ur-series/ur-series_manual_4212129348.webp)
3-132
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
LivLiv
SPS
This data object indicates that both sources are live, and that angle, frequency, and
voltage difference and range conditions have been met
SynChkRSYN
LivLivDpo
SPS
This data object indicates that one or both sources are not live, or that angle,
frequency, and voltage difference and range conditions have been met
SynChkRSYN
LivV1
SPS
This data object indicates that V1 is above the LivVal1 setting
SynChkRSYN
LosLife
MV
LosLifSPTR1
LosLifeRte
MV
LosLifSPTR1
LosPkt1
SPS
The lost packet threshold has been exceeded
LinDfPDIF
MAC
VSG
Expected value of Destination MAC address field in messages subscribed to by
RxGOOSE#
LGOS
MajorErr
SPS
Any of the major self-test errors generated (major error)
LPHD
MaxAsymOp1
SPS
Asymmetry on the channel exceeded pre-set value
LinDfPDIF
MinorErr
SPS
Any of the minor self-test errors generated (minor error)
LPHD
MnlCls
SPS
Manual close initiated
Bkr?XCBR
NegTotVArh
MV
Total VAr-hour in negative direction
EnrMtrMMTR
NegTotWh
MV
Total Watt-hour in negative direction
EnrMtrMMTR
NeutOpn
SPS
Indicates source has lost voltage signal
VtffGAPC
NeutSupn
SPS
Neutral overcurrent supervision status
GndDisPDIS
NumCycPer
INS
Number of cycles of the nominal frequency
OscRDRE
Off
SPS
Logic 0 fixed operand
Master/LLN0
On
SPS
Logic 1 fixed operand
Master/LLN0
OnePoleOpn
SPS
One pole is open, others closed
Bkr?XCBR
OnePU
ASG
The per-unit base factor applied to the corresponding RxGOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity.
GGIO3
OpBia
ACT
B90 Operate indicates the trip decision of a biased protection logic
B_DifPDIF
OpHiSet
ACT
B90 Operate indicates the trip decision of the HISET element of breaker failure current
supervision function.
B_BFaiPIOC
OpLoSet
ACT
B90 Operate indicates the trip decision of the LOSET element of breaker failure current
supervision function.
B_BFaiPIOC
OpnSt1
SPS
Open status detected
Bkr?XCBR,
Disc0XSWI,
Disc?XSWI, GGIO3
OpPhs1
SPS
Indicates a trip decision for a particular cause per phase
BusDifPDIF,
PhsDisPDIS
OpSig
MV
Operating signal, the analogue value used by the comparator
FlxElGAPC
OpUnBia
ACT
B90 Operate indicates the trip decision of an unbiased protection logic
B_DifPDIF
OscilGOOSE
SPS
One or more of GGIO1.Ind###.stVal has been frozen due to frequent status changes
(chatter) in the mapped operand
LPHD
OutOfSrv
SPS
Out-of-service
Bkr?XCBR
P1Rip
SPS
Autoreclose A single pole is in progress
Rec13pRREC
P3Rip1
SPS
Autoreclose 3-pole is in progress via dead time number indicated by the data instance
number
Rec13pRREC
P3Tr
SPS
Force any trip to 3-phase trip
Rec13pRREC
PbCtl
ENG
Front panel pushbutton control Enable/Disable setting: 0 = Disabled, 1 = Enabled
Bkr?XCBR
PFLLfail
SPS
Phase and/or frequency lock loop (PFLL) has failed
LinDfPDIF
PhDir1
SPS
Indicates Phase Comparison of differential is satisfied per phase, where the last digit of
instance number 1, 2, or 3 refers to phase A, B, and C respectively
B_DifPDIF,
BusDifPDIF,
SttDifPDIF
PosTotVArh
MV
Total VAr-hour in positive direction
EnrMtrMMTR
PosTotWh
MV
Total Watt-hour in positive direction
EnrMtrMMTR
Data object
name
CDC
Semantics
Used in logical
nodes…
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...