CHAPTER 3: IEC 61850 COMMUNICATION
PIXIT CONFORMANCE STATEMENT
UR SERIES – COMMUNICATIONS GUIDE
3-137
3
Table 3-121: PIXIT for Server model
Table 3-122: PIXIT for Setting group control model
Table 3-123: PIXIT for Reporting model
As6
1,2
If association parameters are necessary
for association, describe the correct
values
Transport selector 0001
Session selector 0001
Presentation selector 00000001
As7
1,2
What are the maximum and minimum
MMS PDU sizes?
Max MMS PDU size 64000
Min MMS PDU size 13000
As8
1,2
What is the maximum start up time after
a power supply interrupt?
120 seconds
ID
Ed
Description
Value / Clarification
Sr1
1,2
Which analogue value (MX) quality bits are
supported (can be set by server)?
Validity:
Y Good
Y Invalid
N Reserved
Y Questionable
N Overflow
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
Y Test
N OperatorBlocked
Sr2
1,2
Which status value (ST) quality bits are
supported (can be set by server)?
Validity:
Y Good
Y Invalid
N Reserved
Y Questionable
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
Y Test
N OperatorBlocked
ID Ed
Description
Value
/
Clarification
Sg2
1,2
What is the effect of when and how the non-volatile storage is updated
(compare IEC 61850-8-1 $16.2.4)?
Not applicable
Sg6
2
When ResvTms is not present how long is an edit setting group locked? 60 seconds
ID
Ed
Description
Value / Clarification
Rp3
1,2
Can the server send segmented reports?
Y
Rp4
1,2
Mechanism on second internal data change notification of the
same analogue data value within buffer period (Compare IEC
61850-7-2 $14.2.2.9)
Send report immediately
Rp7
1,2
What is the buffer size for each BRCB or how many reports can
be buffered?
Buffer size = 36864 bytes
ID
Ed
Description
Value / Clarification
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...