3-50
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.17 Frequency rate of change (RteHz)
This element is instantiated in the following products: D60, F60, G30, G60, L90, N60, T60.
Table 3-36: Frequency rate of change data objects
3.5.2.18 Ground distance (GndDis)
This element is instantiated in the following products: D30, D60, L60, L90, T60.
Table 3-37: Ground distance data objects
InRef14
ORG
DCUB LOG4 setting (Loss of Guard)
R
setSrcRef
ObjectReference
SP DCUB LOG4
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
RteHzPFRC#
LDevice inst:
Prot
UR element:
Frequency Rate of Change element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
FREQ RATE # PKP operand, which indicates
that Op operates when delay expires
R
general
BOOLEAN
ST FREQ RATE # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
FREQ RATE # OP operand
R
general
BOOLEAN
ST FREQ RATE # OP
R
Dpo
SPS
FREQ RATE # DPO operand
R
stVal
BOOLEAN
ST FREQ RATE # DPO
R
HzChgRte
MV
FREQUENCY RATE OF CHANGE # in Hz/s
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
FREQUENCY RATE OF CHANGE #
R
Mag
AnalogueValue
MX
R
mag.f
FLOAT32
FREQUENCY RATE OF CHANGE #
on deadband exception
R
units
Unit
CF
R
units.SIUint
ENUMERATED
75, the code for Rate of change of
frequency (Hz/s)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF RteHzPFRC#.HzChgRte.db
R/W/C
zeroDb
INT32U
CF
0
R
BlkRef1
ORG
FREQ RATE # BLOCK setting
R
setSrcRef
ObjectReference
SP FREQ RATE # BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
GndDisPDIS#
LDevice inst:
Prot
UR element:
Ground Distance Z# Settings
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
GND DIST Z# PKP operand in Phase –To –
Ground
R
general
BOOLEAN
ST GND DIST Z# PKP
R
dirGeneral
ENUMERATED
ST
1(Forward) if GND DIST Z DIR value is
Forward, 2 (backward) if GND DIST Z1 DIR
value is Reverse, and otherwise 0 (unknown)
R
phsA
BOOLEAN
ST GND DIST Z# PKP A
R
dirPhsA
ENUMERATED
ST dirGeneral
R
phsB
BOOLEAN
ST GND DIST Z# PKP B
R
dirPhsB
ENUMERATED
ST dirGeneral
R
phsC
BOOLEAN
ST GND DIST Z# PKP C
R
dirPhsC
ENUMERATED
ST dirGeneral
R
LNName:
DCUB_PSCH1
LDevice inst:
Prot
UR element:
Directional Comparison Unblocking element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...