   DEESYS TOTAL PRODUCTS GUIDE

MULTI FUNCTION GROUND FAULT 

RELAY [GFR]-5C, 10C

Features

Rating & Specification

1. Multi-ground fault relay(GFR) is multi-functional and is able to detect multiple ground faults of monitoring circuit and is displayed 
   leakage in the circuit and fault current when earthing.
2. It is installed 8 bit MCU with A/D conventer and is configured to perform advanced functions for high relability.
3. It is a collective device that is intergrated many ground fault detector of conventional single unit.
4. It is capable to detect from minor grounding fault current(0.1A) to medium level fault current (10A)
5. It is configured to have operating time taps for adjustment of time setting is easy for protection coordination of distribution circuit
6. As wide display and indicators, it is able to enhance checking up and performance.
7. Watch dog function assures error - free operation.
8. The memory stores the last record of ground fault current of each circuit to facilitate following up in the event of accidents.
9. The ABS casing newly adopted offers improved durability and extended life of product.
10. All GFRs are tested EMC to ensures and high frequency & surge do not interfere design performance of GFR.

DGF-M10

DGF-M10(For 10 Circuits)

for protection against minor and major ground Leakage faults

AC 110/220V Operrable in Common or AC 240V

50/60㎐ Operable in common

9steps, of 0.1, 0.3, 0.5, 1, 2, 3, 5, 10 and Lock T:70% to 100% of current setting

9steps, of 0.05, 0.1, 0.3, 0.5, 1, 2, 3, 5, 10sec T:±10% for 0.05 T=0.1±25㎳

10Circuits

LED (Red) and Digtal Display one for each Circuit

Auto/Manual

-10℃~+50℃

Energized:Full vibration width 4㎜, 1000rpm, 10min

Deenergized:Full vibration width 4㎜, 1000rpm, 10min

Impact strength of 300㎨ applied to 3 axial directions of right & left. up & down, and behind & forward

Opn Cirr-Casing : AC 2000V
Opn Cir-OOpn Cir : AC 2000V
Test Cir-Terminals : AC 1000V

60㎐, 1min

Opn cir-Casing 10㏁ or more
Pon cir-Opn Cir : 10㏁ or more
Test Cir-Terminals : 10㏁ or more

7VA

AC 125V 5A/DC 30V 5A

2.0㎏

ZCT Rating 200㎃/100㎷ (ZR, ZS, ZB type)

Items

Usage

Control Power Voltage

Frequency

Operating current setting

Operating Time setting

Ground Fault Detection Circuit

Operating status Indicator

Resetting

Ambient Temperature

Vibration Resistance

Impact Resistance

Common frequency dielecric 

resistance

Insulating Resistance

Power Consumption

Contact Capacity

Weight

ZCT(input)

DGF-M05(For 5 Circuits)

5Circuits

by DC 500V megger

5VA

1.7㎏

Summary of Contents for DGF-M10

Page 1: ...duct 10 All GFRs are tested EMC to ensures and high frequency surge do not interfere design performance of GFR DGF M10 DGF M10 For 10 Circuits for protection against minor and major ground Leakage faults AC 110 220V Operrable in Common or AC 240V 50 60 Operable in common 9steps of 0 1 0 3 0 5 1 2 3 5 10 and Lock T 70 to 100 of current setting 9steps of 0 05 0 1 0 3 0 5 1 2 3 5 10sec T 10 for 0 05 ...

Page 2: ...urrent setting switch 8 Operating time setting switch 9 Self test button for each circuit 10 Sensing current and operating time 11 Reset button 12 Power lamp 13 Sensing current setting check button 14 Operating time setting check button DGF M05T Combination 1a ARB Contact AC 250V 10A Trip MCCB or Alarm DGF M05 None Direct 1a 5C or 10C AC 250V 10A Trip MCCB Alarm Model DRB 005 010 Contact Contact C...

Page 3: ...perating Time Setting Check Button The button is used to display operating time setting of circuit for checking purpose Outline Information Performance Features 1 Multi ground fault relay monitors a number of circuits collectively and carries built in functional arrangement for ground leakage level indication and fault current level indication 2 It performs monitoring of all circuits consequently ...

Page 4: ...ndicate power suppy 3 Check up digital displays by pressing circuit test switch The circuit number on display changes by advancing one circuit at each of pressing the button and ground fault current level indicator will remain displaying all the while of testing After an elapse of about 25 seconds or so without pressing test button further the indication will disappear automatically 4 Check up ope...

Page 5: ...138 DEESYS TOTAL PRODUCTS GUIDE External contacts wiring diagram Trip contacts Internal block diagram External terminal arrangement MULTI FUNCTION GROUND FAULT RELAY GFR 5C 10C ...

Page 6: ...ntral control board lamp indication It is insulated completely between and among input output and power lines Single board is capable to control 5or 10 circuits Formerly exposed aux relays are now internally located in order to prevent mal functioning caused by moisture hazardous to insulation Features GFR output Inetrnal block diagram T erminal arrangement Rated Specification External wiring diag...

Reviews: