1. Line Check Button

  When the switen is pressed, one by one time monitored 
  circuit number is changed to next circuit number and 
  ground fault current level of the circuit is displayed.

2. Monitored Circuit Indicator(Digital)

  It indicates monitored circuit number in numberals.

3. Earth Leakage Level Indicator

  The level of earth leakage or fault current is displayed.

4. Hold Check Switch(Stored memory of fault current level)

  Pressing hold check switch, earth leakage level indicator is 
  displayed fault current of each circuit.

5. Auto./Manual Switch

  If the switch is set to auto position, warning lamp(Red LED) 
  turns on to warn the status of the switch setting.

6. Ground Fault Indicator Lamp

  The lamp of leaking circuit turns on when self-test button 
  of the same leaking circuit is pressed.

7. Ground Fault Sensing Current Setting Switch

  Select suitable step of sensing current between 0.1 and 10A 
  rating as being reqired by characteristics of a line.
  ※Note : The relay does not operate in case of lock position

8. Operating Time Setting Switch

  The switch is used to set required interval of operating time 
  from 0.05 to 10 seconds.

9. Self-Test Button

  If the button of a circuit is pressed, the status of circuit is 
  simulated to real ground fault and ground fault indicator 
  lamp turns on to alarm fault status.

10. Sensing Current and Operating Time Reference Table

  It is a table of current and time values that can be quoted 
  for current and time setting as the reference.

11. Reset Button

  The button, if pressed, is intialized entire relay function. 

12. Power Lamp(Green LED)

  It turns on when the power of AC110/220V(or AC 240V)is 
  regularly supplied.

13. Sensing Current Setting Check Button

  The button is used to display ground fault sensing current 
  setting for checking purpose.

14. Operating Time Setting Check Button

  The button is used to display operating time setting of circuit 
  for checking purpose.

Outline Information

Performance Features

1. Multi-ground fault relay monitors a number of circuits 
  collectively and carries built-in functional arrangement for 
  ground leakage level indication and fault current level 
  indication.

2. It performs monitoring of all circuits consequently by the    
  command of MCU.

3. In case a ground fault current developed, it induces a    
voltage in ZCT which is fed to ground fault current detection  
  circuit as an input.

4. After Input signal(voltage) is amplified, and then it is 
  supplied to CPU for processing.

5. CPU converts input by A/D converter for comparison to set  
  value of sensing current. And, if it is found more exceeding  
  the setting value, it is performed as followings.
  1) Turns on ground fault indicator lamp upon the elapse of   
     setting interval of operating time.
  2) Activates GFR or the circuit.
  3) Indicates level of ground fault current on ground fault 
     current indicator in numeral value.
  ※Note : If Auto/Manual switch is set to Auto position the 
  warning lamp(Red LED) turns on, and the fault is repaired, all 
  operating indication of the circuit will disappear automatically.

MULTI FUNCTION GROUND FAULT 

RELAY [GFR]-5C, 10C

6. Identification of indications : When leakages occur in plural 
  number of circuits on sometime, ground fault indicator lamps    
  for applicable circuits will light up at once. But ground fault 
  circuit number indicator and ground fault current level 
  indicator  will display the value of first circuit detected. The 
  values of other fault circuits can be checked by pressing 
  circuit test button of respective circuit. If it is the auto reset 
  mode, fault current has been cleared. Such fault current can 
  be read out from the memory by pressing hold check button.

7. Reset If Auto/Manual switch is set to manual position after 
  the ground fault is repaired, press reset button to initialize the     
  performance or else fault indication will be kept on. 

Summary of Contents for DGF-M10

Page 1: ...duct 10 All GFRs are tested EMC to ensures and high frequency surge do not interfere design performance of GFR DGF M10 DGF M10 For 10 Circuits for protection against minor and major ground Leakage faults AC 110 220V Operrable in Common or AC 240V 50 60 Operable in common 9steps of 0 1 0 3 0 5 1 2 3 5 10 and Lock T 70 to 100 of current setting 9steps of 0 05 0 1 0 3 0 5 1 2 3 5 10sec T 10 for 0 05 ...

Page 2: ...urrent setting switch 8 Operating time setting switch 9 Self test button for each circuit 10 Sensing current and operating time 11 Reset button 12 Power lamp 13 Sensing current setting check button 14 Operating time setting check button DGF M05T Combination 1a ARB Contact AC 250V 10A Trip MCCB or Alarm DGF M05 None Direct 1a 5C or 10C AC 250V 10A Trip MCCB Alarm Model DRB 005 010 Contact Contact C...

Page 3: ...perating Time Setting Check Button The button is used to display operating time setting of circuit for checking purpose Outline Information Performance Features 1 Multi ground fault relay monitors a number of circuits collectively and carries built in functional arrangement for ground leakage level indication and fault current level indication 2 It performs monitoring of all circuits consequently ...

Page 4: ...ndicate power suppy 3 Check up digital displays by pressing circuit test switch The circuit number on display changes by advancing one circuit at each of pressing the button and ground fault current level indicator will remain displaying all the while of testing After an elapse of about 25 seconds or so without pressing test button further the indication will disappear automatically 4 Check up ope...

Page 5: ...138 DEESYS TOTAL PRODUCTS GUIDE External contacts wiring diagram Trip contacts Internal block diagram External terminal arrangement MULTI FUNCTION GROUND FAULT RELAY GFR 5C 10C ...

Page 6: ...ntral control board lamp indication It is insulated completely between and among input output and power lines Single board is capable to control 5or 10 circuits Formerly exposed aux relays are now internally located in order to prevent mal functioning caused by moisture hazardous to insulation Features GFR output Inetrnal block diagram T erminal arrangement Rated Specification External wiring diag...

Reviews: