background image

1 / 2

HRF-10

cos φ ≥ 0.95

M

M

HAL.230V

K

M

M

AC12

250V / 1A

DC14

x

AC1

250V / 8A

AC13

x

AC2

250V / 3A

AC14

250V / 3A

AC3

250V / 2A

AC15

250V / 3A

AC5b

300W

DC5

24V / 2A

AC6a

x

DC12

24V / 8A

AC7b

250V / 1A

DC13

24V / 2A

02-15/2017 Rev.: 0

1

6

7
8

5

2

3

9

10

4

16   15  18   28  25   26

                               N     L

L

N

DC1

24V / 8A

DC3

24V / 3A

Made in Czech Republic

ELKO EP, s.r.o. 

Palackého 493
769 01 Holešov, Všetuly
Czech Republic 
Tel.: +420 573 514 211
e-mail: [email protected]
www.elkoep.com

Frequency monitoring relay

• 

the relay serves to monitor frequency of AC voltage, e.g. in photovoltaic power 
stations, generators

• 

the monitored frequency 50 / 60 / 400 Hz is selected by a switch

• 

supplied from monitored voltage

• 

two adjustable levels of frequency (Fmin, Fmax) in the range of 80 - 120 % Fn

• 

adjustable diff erence level

• 

adjustable delay level

• 

switchable ranges of rated frequency Fn

• 

3-MODULE design, DIN rail mounting

Characteristics 

Description

Connection

Type of load

Mat. contacts AgNi, 

contact 8A

Type of load

Mat. contacts AgNi, 

contact 8A

AC5a 

uncompensated

230V/1.5A (345VA)

AC5a

compensated

x

EN

1. Supply voltage indication
2. Indication F > Fmax
3. Indication F < Fmin
4. Output contact
5. Supply / monitored voltage terminals
6. Delay setting
7. Diff erence setting
8. Fmax setting
9. Fn setting
10. Fmin setting