CHAPTER 3: IEC 61850 COMMUNICATION
PIXIT CONFORMANCE STATEMENT
UR SERIES – COMMUNICATIONS GUIDE
3-139
3
Table 3-127: PIXIT for Control model
Gf3
1,2
Application logic scan cycle (ms)
Max.
1/8 cycle (2.0 ms @60 Hz, 2.5
ms @50 Hz) or 100 ms
(configurable)
Min.
ID
Ed
Description
Value / Clarification
Ct2
1,2
Is the control model fixed, configurable and/
or dynamic?
Fixed, Configurable, or Dynamic depending on
the particular control point
Ct9
1,2
Which additional cause diagnosis are
supported?
N Unknown
Y Not-supported
Y Blocked-by-switching-hierarchy
Y Select-failed
Y Invalid-position
Y Position-reached
N Parameter-change-in-execution
N Step-limit
Y Blocked-by-Mode
N Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
N Time-limit-over
N Abortion-by-trip
Y Object-not-selected
Edition 2 specific values:
Y Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
Y Blocked-by-command
N None
Y Inconsistent-parameters
Y Locked-by-other-client
Ct10
1,2
How to force a “test-not-ok” respond with
SelectWithValue request
Not possible
Ct11
1,2
How to force a “test-not-ok” respond with
Select request
Not possible
Ct12
1,2
How to force a “test-not-ok” respond with
Operate request
DOns:
SBOns:
DOes:
SBOes:
As per IEC 61850-8-1, clause 20.11 (“Operator
Test Not OK” shall be returned if an Operate
control command is issued, with TEST=TRUE,
and the operation fails.)
Ct13
1,2
Which origin categories are supported /
accepted?
Y bay-control
Y station-control
Y remote-control
Y automatic-bay
Y automatic-station
Y automatic-remote
Y maintenance
Y process
Ct14
1,2
What happens if the orCat value is not
supported or invalid?
DOns: Operate fails
SBOns: Operate fails
DOes: Operate fails
SBOes: Select fails
ID
Ed
Description
Value / Clarification
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...