![background image](http://html1.mh-extra.com/html/ge/ur-series/ur-series_manual_4212129237.webp)
CHAPTER 3: IEC 61850 COMMUNICATION
ACSI CONFORMANCE STATEMENT
UR SERIES – COMMUNICATIONS GUIDE
3-21
3
3.4.2 ACSI models conformance statement
The table contains the conformance statement.
Table 3-5: ACSI models conformance statement
B22
SCSM: IEC 61850-9-1 used
deprecated
B23
SCSM: IEC 61850-9-2 used
B24
SCSM: other
Generic substation event model (GSE)
B31
Publisher side
Yes
B32
Subscriber side
Yes
Transmission of sampled value model (SVC)
B41
Publisher side
B42
Subscriber side
Client / subscriber Server / publisher Value / comments
M1
Logical device
Yes
M2
Logical node
Yes
M3
Data
Yes
M4
Data set
Yes
M5
Substitution
M6
Setting group control
Yes
Reporting
M7
Buffered report control
Yes
M7-1
sequence-number
Yes
M7-2
report-time-stamp
Yes
M7-3
reason-for-inclusion
Yes
M7-4
data-set-name
Yes
M7-5
data-reference
Yes
M7-6
buffer-overflow
Yes
M7-7
entryID
Yes
M7-8
BufTm
Yes
M7-9
IntgPd
Yes
M7-10
GI
Yes
M7-11
conf-revision
Yes
M8
Unbuffered report control
Yes
M8-1
sequence-number
Yes
M8-2
report-time-stamp
Yes
M8-3
reason-for-inclusion
Yes
M8-4
data-set-name
Yes
M8-5
data-reference
Yes
M8-6
BufTm
Yes
M8-7
IntgPd
Yes
M8-8
GI
Yes
M8-9
conf-revision
Yes
Logging
M9
Log control (LCB)
Client / subscriber Server / publisher Value / comments
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...