Solid State Relays with Failure Detection Function

 

G3PC

J-59

SSR

Solid State Relays with Failure Detection Function

G3PC

Detects failures in SSR used for heater 
temperature control and simultaneously 
outputs alarm signal. This SSR supports the 
safe design of heater control systems, and 
contributes to maintenance improvements 
by the user.

• Main detection items:

SSR short-circuits and SSR open-circuits

• Alarm output possible to NPN/PNP-input devices.

• The failure-detection function is built-in and power is supplied 

from the main circuit power supply making wiring simple.

• Slim design (width: 22.5 mm) incorporating a heat sink.

• In addition to screw mounting, DIN track mounting is also 

possible.

• Certified by EC, UL, and CSA.

Model Number Structure

Model Number Legend

1. Basic Model Name

G3PC:

SSR with Failure Detection Function

2. Rated Load Power Supply Voltage

2:

100 to 240 VAC

3. Rated Load Current

20:

20 A (carry current)

4. Terminal Type

B:

Screw terminals

5. Certification

VD:

Certified by UL, CSA, and VDE

Ordering Information

List of Models

Note:

When ordering, specify the rated input voltage.

Accessories (Order Separately)

1

2 3 4

5

G3PC-

@@@-@

Insulation method

Zero cross function

Indicators

Rated output load

Model number

Phototriac coupler

Yes

Yes 
(See page 64)

20 A, 100 to 240 VAC
(resistive load: AC, Class1)

G3PC-220B-VD

Name

Dimensions

Model number

Mounting Track

50 cm (

l

×

 7.3 mm (t)

PFP-50N

1 m (

l

×

 7.3 mm (t)

PFP-100N

1 m (

l

×

 16 mm (t)

PFP-100N2

Summary of Contents for G3PC

Page 1: ...a heat sink In addition to screw mounting DIN track mounting is also possible Certified by EC UL and CSA Model Number Structure Model Number Legend 1 Basic Model Name G3PC SSR with Failure Detection F...

Page 2: ...N open collector Operate time 1 2 of load power source cycle 1 ms max Release time 1 2 of load power source cycle 1 ms max Main circuit Output ON voltage drop 1 6 V rms max OFF leakage current 10 mA m...

Page 3: ...00 150 200 250 The figure will be less than 1 2 the rated value for repetitive input One Cycle Surge Current Non repetitive Load Current vs Ambient Temperature Input Voltage vs Input Current Input Vol...

Page 4: ...on Note 1 With 3 phase connection so that the power supply voltage is applied between the G3PC s terminals 1 L1 and 3 connect the desired phase to terminal 3 2 Above mentioned products are 200V only T...

Page 5: ...he above diagram is for when the terminal cover is closed 4 6x5 6 elliptic hole 130 max 1 100 max 22 5 max Terminal cover Tow 4 6 dia Three 4 5 dia or M4 4 5 15 25 10 25 25 25 10 1 000 500 7 3 0 15 35...

Page 6: ...3 With inductive loads relay coil etc connect back current prevention diodes to both sides of the load Terminal name Terminal number Screw size Main circuit terminals output 1 L1 2 T1 M4 Detection pow...

Page 7: ...te Use the G3PC at a load current of 80 of the rated load current when it is mounted side by side Wiring When using crimp terminals observe the terminal clearances shown below Make sure that all lead...

Page 8: ...3PC In the interest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert...

Reviews: