Ground Fault Relay

K6EL

Economical, Compact, High-performance, 
DIN 48 

u

 48-mm Ground Fault Relay for Low 

Voltages

• Performs continuous monitoring and detection of ground faults 

in low-voltage circuits due to the deterioration of insulation in 
electrical devices.

• Higher reliability ensured with improved resistance to high-fre-

quency noise when used for inverter loads.

• Remote monitoring of cubicles is possible with automatic-reset 

models.

• Ground Fault Relays and through-type ZCTs (zero-phase cur-

rent transformers) are mutually compatible.

• The through-type ZCTs are equipped with test terminals, allow-

ing operation tests for Ground Fault Relays to be performed with 
ease.

• Series now includes K6EL-R50, which operates at 

50 mA

r

10%.

Model Number Structure

Model Number Legend

1. Ground Fault Relay
2. Operating Time and Reset Method

None: 0.1 s manual reset 
A:

0.3/0.8 s (switchable) manual reset

R:

0.5 s automatic reset

3. Sensed Current

30:

30 mA (fixed)

50:

50 mA/150 mA (switchable)

100: 100 mA/200 mA (switchable)
200: 200 mA/500 mA (switchable)
500: 500 mA/1,000 mA (switchable)

Ordering Information

List of Models

Manual-reset Ground Fault Relays

Automatic-reset Ground Fault Relays

Note:

Operating Error
50-mA tap: 

r

10%

150-mA tap: 

r

20%

2 3

1

K6EL-

@@

Type

Operating time

Type

High-sensitivity 

models

Medium-sensitivity models

Sensed current

30 mA (fixed)

100 mA/200 mA 

(switchable)

200 mA/500 mA 

(switchable)

500 mA/1,000 mA 

(switchable)

High-speed models

Less than 0.1 s

K6EL-30

K6EL-100

K6EL-200

K6EL-500

Delayed models

0.3/0.8 s (switchable)

---

K6EL-A100

K6EL-A200

K6EL-A500

Type

Operating time

Type

High-sensitivity models

Medium-sensitivity models

Sensed current

50 mA/150 mA (switchable)

500 mA/1,000 mA (switchable)

Delayed models

Less than 0.5 s

---

K6EL-R500

K6EL-R50 (See note.)

---

Summary of Contents for K6EL

Page 1: ...Number Structure Model Number Legend 1 Ground Fault Relay 2 Operating Time and Reset Method None 0 1 s manual reset A 0 3 0 8 s switchable manual reset R 0 5 s automatic reset 3 Sensed Current 30 30...

Page 2: ...OK OK OTG L30 100 A OK OK OTG L42 200 A OK OK OTG L68 400 A OK OTG L82 600 A OK OTG L156 1 000 A OK OTG CN52 200 A OK OTG CN77 400 A OK OTG CN112 600 A OK Model Y92F 30 Y92F 71 Model Y92A 48B Hard Co...

Page 3: ...arts and the mounting panel Lightning impulse dielectric strength 1 2 50 Ps 7 000 V between control power supply terminals Lightning impulse operation failure 1 2 50 Ps 7 000 V primary side of ZCT Vib...

Page 4: ...110 V See note 1 See note 2 Operation at 200 220 V Note 1 The K6EL R50 does not have terminals 6 and 7 2 The K6EL R500 and K6EL R50 do not have terminal 2 They cannot be used at 200 220 V POWER SENSIT...

Page 5: ...wise indicated Ground Fault Relay Load Y b Auxiliary relay Alarm buzzer 100 110 VAC 200 220 VAC Y BZ Transformer Molded case circuit breaker 6 5 4 3 2 1 11 10 9 8 7 kt k l lt OTG ZCT K6EL Ground Fault...

Page 6: ...te Recommended panel thickness 1 to 3 2 mm Y92F 30 Flush Mounting Adapter Sold Separately Y92F 71 Flush Mounting Adapter Sold Separately P2CF 11 sold separately PL11 sold separately 103 K6EL 77 7 16 K...

Page 7: ...pitch 136 68 dia 118 17 31 9 3 11 6 1 Mounting Hole Cutout Dimensions Two 5 dia holes or two M4 screw holes 97 107 97 mounting pitch 25 109 88 17 42 dia 11 9 3 5 2 Mounting Hole Cutout Dimensions kt k...

Page 8: ...7 Mounting Hole Cutout Dimensions 9 263 156 dia 138 3 2 270 230 60 M5 terminal screws 130 90 20 40 L 230 90 Mounting Hole Cutout Dimensions Four 8 5 dia holes or four M8 screw holes K K M4 terminal sc...

Page 9: ...2 325 mm2 325 mm2 250 mm2 OTG L82 600 A 82 dia 500 mm2 500 mm2 400 mm2 400 mm2 OTG L156 1 000 A 156 dia 500 mm2 500 mm2 1 000 mm2 1 000 mm2 OTG CN52 200 A 52 dia 200 mm2 200 mm2 150 mm2 100 mm2 OTG CN...

Page 10: ...as possible or use a shield line When installing a separate type ZCT with current flowing along the primary conductors short the secondary terminals using clips or some other method Switching the Sen...

Page 11: ...as for calculating ground currents for complete ground faults Depending on the location the allowable ground fault current may be restricted In this case use values of R and C that do not exceed the r...

Page 12: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syste...