background image

http://www.ia.omron.com/

9

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

K6EL

Maximum Wire Sizes for ZCTs

Wire/cable

600-V vinyl-insulated wire (IV)

Cable (VVR)

Model

Rated 

current

Through-hole 

diameter

2-wire

3-wire

2-wire

3-wire

OTG-L21

50 A

21 dia.

22 mm

2

14 mm

2

8 mm

2

5.5 mm

2

OTG-L30

100 A

30 dia.

60 mm

2

38 mm

2

38 mm

2

38 mm

2

OTG-L42

200 A

42 dia.

100 mm

2

100 mm

2

100 mm

2

60 mm

2

OTG-L68

400 A

68 dia.

400 mm

2

325 mm

2

325 mm

2

250 mm

2

OTG-L82

600 A

82 dia.

500 mm

2

500 mm

2

400 mm

2

400 mm

2

OTG-L156

1,000 A

156 dia.

500 mm

2

500 mm

2

1,000 mm

2

1,000 mm

2

OTG-CN52

200 A

52 dia.

200 mm

2

200 mm

2

150 mm

2

100 mm

2

OTG-CN77

400 A

77 dia.

500 mm

2

400 mm

2

400 mm

2

325 mm

2

OTG-CN112

600 A

112 dia.

500 mm

2

500 mm

2

1,000 mm

2

1,000 mm

2

K

K

M4 terminal screws

84

77 dia.

157

230

195

70 53

7

195

53

Mounting Hole

Cutout Dimensions

Four, 6.5-dia. holes or
four, M6 screw holes

K

K

260

225

70 53

7

112 dia.

M4 terminal screws

107

200

225

53

Mounting Hole

Cutout Dimensions

Four, 6.5-dia. holes or
four, M6 screw holes

OTG-CN77 (400 A)

OTG-CN112 (600 A)

Summary of Contents for K6EL

Page 1: ...Number Structure Model Number Legend 1 Ground Fault Relay 2 Operating Time and Reset Method None 0 1 s manual reset A 0 3 0 8 s switchable manual reset R 0 5 s automatic reset 3 Sensed Current 30 30...

Page 2: ...OK OK OTG L30 100 A OK OK OTG L42 200 A OK OK OTG L68 400 A OK OTG L82 600 A OK OTG L156 1 000 A OK OTG CN52 200 A OK OTG CN77 400 A OK OTG CN112 600 A OK Model Y92F 30 Y92F 71 Model Y92A 48B Hard Co...

Page 3: ...arts and the mounting panel Lightning impulse dielectric strength 1 2 50 Ps 7 000 V between control power supply terminals Lightning impulse operation failure 1 2 50 Ps 7 000 V primary side of ZCT Vib...

Page 4: ...110 V See note 1 See note 2 Operation at 200 220 V Note 1 The K6EL R50 does not have terminals 6 and 7 2 The K6EL R500 and K6EL R50 do not have terminal 2 They cannot be used at 200 220 V POWER SENSIT...

Page 5: ...wise indicated Ground Fault Relay Load Y b Auxiliary relay Alarm buzzer 100 110 VAC 200 220 VAC Y BZ Transformer Molded case circuit breaker 6 5 4 3 2 1 11 10 9 8 7 kt k l lt OTG ZCT K6EL Ground Fault...

Page 6: ...te Recommended panel thickness 1 to 3 2 mm Y92F 30 Flush Mounting Adapter Sold Separately Y92F 71 Flush Mounting Adapter Sold Separately P2CF 11 sold separately PL11 sold separately 103 K6EL 77 7 16 K...

Page 7: ...pitch 136 68 dia 118 17 31 9 3 11 6 1 Mounting Hole Cutout Dimensions Two 5 dia holes or two M4 screw holes 97 107 97 mounting pitch 25 109 88 17 42 dia 11 9 3 5 2 Mounting Hole Cutout Dimensions kt k...

Page 8: ...7 Mounting Hole Cutout Dimensions 9 263 156 dia 138 3 2 270 230 60 M5 terminal screws 130 90 20 40 L 230 90 Mounting Hole Cutout Dimensions Four 8 5 dia holes or four M8 screw holes K K M4 terminal sc...

Page 9: ...2 325 mm2 325 mm2 250 mm2 OTG L82 600 A 82 dia 500 mm2 500 mm2 400 mm2 400 mm2 OTG L156 1 000 A 156 dia 500 mm2 500 mm2 1 000 mm2 1 000 mm2 OTG CN52 200 A 52 dia 200 mm2 200 mm2 150 mm2 100 mm2 OTG CN...

Page 10: ...as possible or use a shield line When installing a separate type ZCT with current flowing along the primary conductors short the secondary terminals using clips or some other method Switching the Sen...

Page 11: ...as for calculating ground currents for complete ground faults Depending on the location the allowable ground fault current may be restricted In this case use values of R and C that do not exceed the r...

Page 12: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syste...

Reviews: