GD350A series high-performance multifunction VFD
-54-
Note: If fault occurred, rule out the fault cause according to "fault tracking".
The running command channel can be set by terminal commands besides P00.01 and P00.02.
Current running
command channel
P00.01
Multi-function
terminal function (36)
Command switches
to keypad
Multi-function terminal
function (37)
Command switches to
terminal
Multi-function terminal
function (38)
Command switches to
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note:
"/" means this multi-function terminal is valid under current reference channel.
Related parameter list:
Function
code
Name
Description
Default
Speed control
mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note: To select 0, 1, or 3 as the control mode,
enable the VFD to perform motor parameter
autotuning first.
2
Channel of
running
commands
0: Keypad
1: Terminal
2: Communication
0
Communication
mode of running
commands
0: Modbus/Modbus TCP
1: Profibus/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/Profinet/EtherNetIP
4: Programmable expansion card
5: Wireless communication card
0
Motor parameter
autotuning
0: No operation
1: Rotary autotuning.
Comprehensive motor parameter autotuning. It
is recommended to use rotating autotuning
when high control accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in cases
0