GD350A series high-performance multifunction VFD
-301-
Function
Address
Data description
R/W
0007H: Fault reset
0008H: Jogging to stop
Communication-based
value setting
2001H
Communication-based frequency setting (0–
Fmax, unit: 0.01 Hz)
R/W
2002H
PID setting, range (0–1000, 1000
corresponding to 100.0%)
In the actual operation, set P00.01 to 2 and P00.06 to 8.
The command transmitted by the master is as follows:
Parameter
address
VFD
address
Continuous
write
command
Number of
bytes
Parameter
quantity
01
10
20 00 00 02
04
Froward
running
00 01
10 Hz
03 E8
CRC
3B 10
If the operation is successful, the following response is returned:
Parameter
address
VFD
address
Continuous
write
command
CRC
Parameter
quantity
01 10
20 00 00 02 4A 08
Example 2: Set "ACC time" of the VFD whose address is 01H to 10s, and "DEC time" to 20s.
P00.11 ACC time 1
Setting range of P00.11 and P00.12: 0.0–3600.0s
Model
depended
○
P00.12 DEC time 1
Model
depended
○
The address of P00.11 is 000B, 10s is 0064H in the hexadecimal form, and 20s is 00C8H in the
hexadecimal form.
The command transmitted by the master is as follows:
Parameter
address
VFD
address
Continuous
write
command
Number of
bytes
Parameter
quantity
01
10
00 0B 00 02
04
10s
00 64
20s
00 C8
CRC
F2 55
If the operation is successful, the following response is returned: