![Esco invt GD350A Series Product Manual Download Page 296](http://html1.mh-extra.com/html/esco/invt-gd350a-series/invt-gd350a-series_product-manual_2426081296.webp)
GD350A series high-performance multifunction VFD
-291-
regardless of the VFD status. Pay attention to the setting range, unit, and description of a
parameter when modifying it.
The service life of the Electrically Erasable Programmable Read-Only Memory (EEPROM) may
be reduced if it is frequently used for storage. Some function codes do not need to be stored
during communication. The application requirements can be met by modifying the value of the
on-chip RAM, that is, modifying the MSB of the corresponding function code address from 0 to
1. For example, if P00.07 is not to be stored in the EEPROM, you need only to modify the value
in the RAM, that is, set the address to 8007H. The address can be used only for writing data to
the on-chip RAM, and it is invalid when used for reading data.
9.4.5.2 Description of other function addresses
In addition to modifying the parameters of the VFD, the master can also control the VFD, such as
starting and stopping it, and monitoring the operation status of the VFD. The following table describes
other function parameters.
Function
Address
Data description
R/W
Communication-based
control command
2000H
0001H: Forward running
R/W
0002H: Reverse running
0003H: Forward jogging
0004H: Reverse jogging
0005H: Stop
0006H: Coast to stop (emergency stop)
0007H: Fault reset
0008H: Jogging to stop
Communication-based
value setting
2001H
Communication-based frequency setting (0–Fmax,
unit: 0.01 Hz)
R/W
2002H
PID setting, range (0–1000, 1000 corresponding to
100.0%)
2003H
PID feedback, range (0–1000, 1000 corresponding
to 100.0%)
R/W
2004H
Torque setting (-3000 – +3000, 1000
corresponding to 100.0% of the motor rated
current)
R/W
2005H
Setting of the upper limit of the forward running
frequency (0–Fmax, unit: 0.01 Hz)
R/W