GD350A series high-performance multifunction VFD
-158-
Function
code
Name
Description
Default Modify
5: Modbus/Modbus TCP communication
(same as the above)
6: Profibus/CANopen/DeviceNet
communication (same as the above)
7: Ethernet communication (same as the
above)
8: Pulse frequency HDIB (same as the above)
9: EtherCat/Profinet/EthernetIP
communication
10: Programmable expansion card
11: Reserved
P03.20
Electromotive
torque upper limit
set through keypad
The function codes are used to set torque
limits.
Setting range: 0.0–300.0% (of the motor rated
current)
180.0%
○
P03.21
Braking torque
upper limit set
through keypad
180.0%
○
P03.22
Weakening
coefficient in
constant power
zone
Used when the AM is in flux-weakening
control.
T
f
0.1
Flux-weakening
coefficient of motor
1.0
2.0
Min. flux-weakening limit of motor
The function codes P03.22 and P03.23 are
valid at constant power. The motor enters the
flux-weakening state when the motor runs
above the rated speed. Change the flux-
weakening curvature by modifying the flux-
weakening control coefficient. The larger the
coefficient, the steeper the curve, the smaller
the coefficient, the smoother the curve.
Setting range of P03.22: 0.1–2.0
Setting range of P03.23: 10%–100%
0.3
○
P03.23
Lowest weakening
point in constant
power zone
20%
○
P03.24 Max. voltage limit P03.24 sets the max. output voltage of the 100.0%
○