GD350A series high-performance multifunction VFD
-206-
Function
code
Name
Description
Default Modify
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0–200.0%
Setting range of P11.07: 0.00–50.00Hz/s
P11.08
Pre-alarm selection
for VFD/motor
OL/UL
0x000–0x1132
Ones place:
0: Motor overload/underload pre-alarm,
relative to rated motor current;
1: VFD overload/underload pre-alarm, relative
to rated VFD current.
Tens place:
0: The VFD continues running after
overload/underload alarm;
1: The VFD continues running after underload
alarm, and stops running after overload fault;
2: The VFD continues running after overload
alarm, and stops running after underload fault;
3: The VFD stops running
after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
0x000
○
P11.09
Overload pre-alarm
detection level
If the VFD or motor output current is larger
than the overload pre-alarm detection level
(P11.09), and the duration exceeds the
overload pre-alarm detection time (P11.10),
G type:
150%
P type:
120%
○